Features and Specifications
Specifications
18
Operating Manual for XKW 1kW Series Power Supply
Table 1.3
Electrical Specifications for 80 V to 600 V Models
Models
80-13
150-7
300-3.5
600-1.7
Output Ratings:
Output Voltage
Output Current
Output Power
0-80 V
0-125 A
1040 W
0-150 V
0-7 A
1050 W
0-300 V
0-3.5 A
1050 W
0-600 V
0-1.7 A
1020 W
Line Regulation:
1
Voltage
Current
1. For input voltage variation over the AC input voltage range, with constant rated load.
80 mV
13 mA
150 mV
7 mA
300 mV
3.5 mA
600 mV
1.7 mA
Load Regulation:
2
Voltage
Current
2. For 0-100% load variation, with constant nominal line voltage.
80 mV
13 mA
150 mV
7 mA
300 mV
3.5 mA
600 mV
1.7 mA
Meter Accuracy:
Voltage
Current
0.9 V
0.23 A
1.6 V
0.08 A
4.0 V
0.045 A
7.0 V
0.018 A
OVP Adjustment Range:
4-88 V
7.5-165 V
15-330 V
30-660 V
Output Noise and Ripple:
(20 Hz - 20 MHz)
Voltage (p-p)
Voltage (rms)
150 mV
20 mV
200 mV
30 mV
200 mV
40 mV
500 mV
100 mV
Drift:
3
Voltage
Current
3. Maximum drift over 8 hours with constant line, load and temperature, after 90 minute warm-up.
40 mV
6.5 mA
75 mV
3.5 mA
150 mV
1.75 mA
300 mV
0.85 mA
Temperature Coefficient:
4
Voltage
Current
4. Change in output per
°
C change in ambient temperature, with constant line and load.
16 mV
3.9 mA
30 mV
2.1 mA
60 mV
1.05 mA
120 mV
0.51 mA
Nominal Output Capacitance:
3,000
µ
F
440
µ
F
440
µ
F
4.7
µ
F
Nominal Capacitance
(Output to Chassis):
250n
F
250n
F
270n
F
220n
F