Operation
Remote Programming of Output Voltage and Current Limit
48
Operating Manual for XKW 1kW Series Power Supply
Programming
With External
Voltage
Sources
The
output voltage
can be programmed using either a 0-5Vdc or 0-10Vdc external
voltage source. To program the output voltage with a 0-5Vdc source, set switch
SW1-3 open (default factory setting) and remove the jumpers connecting pins 8 to 9
and 20 to 21 on connector J3. Connect the external source between pins 9 (positive)
and 12 (return). Varying the external voltage from 0-5V will cause the output to vary
from 0-100% of rated output.
Figure 3.7
SW1/J3 Configuration for 0-5V Programming of the Output Voltage
(J3 sense line, OVP and current control jumpers shown set for local operation)
For programming with a 0-10Vdc source, close switch SW1-3 and replace the 0-5V
source with a 0-10V source.
Figure 3.8
SW1/J3 Configuration for 0-10V Programming of the Output Voltage
(J3 sense line, OVP and current control jumpers shown set for local operation)