Configuring Battery Characteristics and Battery Charging
975-0400-01-01
3–7
Max Absorb Time
180min
120–360 min
180 min
Sets the maximum time spent at
a constant voltage (the setting
for Absorption voltage) during
the absorption stage. This setting
does not control the duration of
the entire Absorption stage.
Force State
Bulk
Bulk, Float, No
Float
Bulk
Manually sets the charge stage to
bulk, float, or no float.
Dflt Batt Temp
Warm
Cold, Warm, Hot Warm
Sets the default battery
temperature for compensation
when the BTS is not connected.
Cold is suitable for temperatures
of around 10 °C (50 °F), Warm
for 25 °C (77 °F), and Hot for
40 °C (104 °F). This screen
appears only when a BTS is not
connected.
Battery Temp
30C
-40–65 C
n/a
Shows the battery temperature
(in Celsius) detected by the BTS.
This screen appears only when a
BTS is connected.
Charge Cycle
3 Stage
3 Stage,
2 Stage No Float
3 Stage
Selects the charging cycle (or
algorithm)—3 Stage (Bulk/
Absorption/Float) or 2 Stage
(Bulk/Absorption/No Float).
Table 3-2
Battery Menu Values
Setting
Values
Default
Description
Summary of Contents for XW-MPPT60-150