background image

 

NOTE: ASOL-250P-WSR MODULES ARE “A” CLASS APPLICATION DEVICES. MAXIMUM 
SYSTEM VOLTAGE 1000 VDC. 

ASOL-250P-WSR series modules and most PV system components have a maximum system voltage rating of 
1000 volts DC. Some grid feed in systems operate at or near this voltage rating. Like other polycrystalline solar 
modules,  the  open  circuit  voltage  of  the  ASOL-250P-WSR  series  modules  increases  as  the  ambient 
temperature decreases. Maximum system voltage is computed as the sum of the open-circuit voltage of the 
series-connected  photovoltaic  modules  for  the  lowest  expected  ambient  temperature.  Temperature 
coefficients, specific to the module of use, can be used to provide the most accurate prediction of module 
voltage under temperature extremes

 
NOTE:

 

Install  the  maximum  number  of  series  for  the  ASOL-250P-WSR  series  modules  so  that  the  system 

voltage is less than 1000 V. XDISC S.A. recommends to connect less than twenty modules in series to keep 
safe voltage rate in the system. 
XDISC S.A. does not recommend connecting modules in parallel configuration due to damage or destruction 
of modules. 

 
NOTE:

 

In normal conditions, PV modules may produce larger current and/or voltage than reported in the 

standard test conditions. Therefore, when voltage evaluations for components, capacity of conductors, size of 
fuses,  and  size  of  control  systems  connected  to  the  module  output  are  determined,  multiply  the  values  of 
short- circuit current (I

sc

) and

 

open-circuit voltage (V

oc

) that are marked in ASOL-250P-WSR series modules by 

the coefficient, 1.25. 
Before  installing  your  system,  contact  local  authorities  to  determine  the  necessary  permit,  installation  and 
inspection requirements

INSTRUCTIONS ON CABLING 

The modules are supplied ex works with a solar cable, 4 mm² including connector and an installation coupling 
to the MC 4 system power socket

-

 

Ensure that the maximum system values for voltage and current are not exceeded. 

-

 

When connecting modules in series ensure that the modules have the same current, the same alignment 
and inclination. 

-

 

When interconnecting the modules ensure that the maximum string voltage does not exceed the 
maximum system voltage of the respective module type (for values refer to the data sheet of the 
corresponding module). 

-

 

Do not open the power socket. 

-

 

Avoid large cable loops. 

-

 

Ensure that the polarity is correct. 

-

 

Use only suitable connectors (MC 4). 

-

 

Use only a suitable solar cable with a correspondingly suitable conductor cross-section (min. 4 mm², 
copper). 

-

 

Protect the cables against direct solar irradiation. 

-

 

Before commissioning the overall system check that the cabling and the DC voltages are correct. 

-

 

Fasten the cables with cable ties that are resistant to ultraviolet rays (e.g. to the mounting frame). 

Summary of Contents for ASOL-250P-WSR

Page 1: ...MOUNTING INSTRUCTION for PHOTOVOLTAIC MODULES Type ASOL 250P WSR ...

Page 2: ...UNDING 6 ELECTRICAL SPECIFICATIONS 6 By pass diode specifications 6 LOCATION SELECTION 6 MODULE TILT ANGLE 6 MOUNTING OF THE MODULES 7 Clips location 7 Mounting with screws 9 MAINTENANCE OF PHOTOVOLTAIC MODULES ASOL 250P WSR 9 Periodic cleaning of the module 9 Visual inspection 9 Connection and wiring controls 10 Manufacturer 10 ...

Page 3: ...d professional manner Electrical work should be performed by a qualified electrician WARNING This photovoltaic module produces electricity when exposed to the sun or other light sources The electrical hazard from the voltage and current of a single module is low However the voltage increases as modules are connected in series and the available current increases as modules are connected in parallel...

Page 4: ...uch the terminals with bare hands Use insulated tools when wiring to solar module terminals wear rubber gloves to eliminate shock or burn potential when wiring solar modules Regardless of whether you are working on a new or existing roof never allow the sheathing and metal parts to become wet Protect the sheathing and metal parts from rain during the installation Failure to do so may cause leaks W...

Page 5: ...for components capacity of conductors size of fuses and size of control systems connected to the module output are determined multiply the values of short circuit current Isc and open circuit voltage Voc that are marked in ASOL 250P WSR series modules by the coefficient 1 25 Before installing your system contact local authorities to determine the necessary permit installation and inspection requir...

Page 6: ...st Conditions rated power Accordingly when determining component ratings and capacities the module short circuit current at STC should be multiplied by 1 25 and a correction factor should be applied for the open circuit voltage An additional 1 25 multiplier for the short circuit current for a total of 1 56 for sizing conductors and fuses may be applicable depending on your local regulations BY PAS...

Page 7: ... location RECOMENDED TILT ANGLES FOR A FIXED SYSTEM SITE LATITUDE IN DEGREES FIXED TILT ANGLE 0 to 15 15 15 to 25 SAME AS LATITUDE 25 to 30 LATITUDE 5 30 to 35 LATITUDE 10 35 to 40 LATITUDE 15 40 LATITUDE 20 MOUNTING OF THE MODULES CLIPS LOCATION XDISC S A recommends using typical aluminium clips designed for framed modules ASOL 250P WSR module mounting configurations must meet the following requi...

Page 8: ...e mounted and must not cause any twist or stress to be placed on the module Modules should be secured to mounting structure using four aluminium at least 80 mm long module clips The retaining clips must each provide a minimum contact area of 10 mm x 80 mm The centre of mounting clips must be located on the long side of the module between 350 mm and 400 mm from the edge See following figure for all...

Page 9: ...d on the transparent cover of the module reduces its performance and can produce reverse effects similar to those produced by shading The problem can become serious in the case of industrial waste or waste caused by birds The intensity of the effects depends on the opaqueness of the residue The layers of dust that reduce the intensity of the sun are not dangerous and the reduction in power is not ...

Page 10: ... wiring Also check to be sure that mounting hardware is tight Loose connections will result in damage for array Do not touch live parts of cables and connectors Use appropriate safety equipment insulated tools insulating gloves etc when touching them Cover the front surface of the Module by an opaque or other material when repairing The ASOL 250P WSR modules when exposed to sunlight generate high ...

Reviews: