FusionServer 2488H V5 Server
Technical White Paper
6 Product Specifications
Issue 07 (2023-04-30)
Copyright © xFusion Digital Technologies Co., Ltd.
63
Component
Specifications
⚫
Secure boot
⚫
Front bezel (optional)
6.2 Environmental Specifications
Table 6-2
Environmental specifications
Category
Specifications
Temperature
⚫
Operating temperature: 5°C to 45°C (41°F to 113°F)
(ASHRAE Classes A1 to A4 compliant)
⚫
Storage temperature (within three months):
–30°C to
+60°C (
–22°F to +140°F)
⚫
Storage temperature (within six months):
–15°C to
+45°C (5°F to 113°F)
⚫
Storage temperature (within one year):
–10°C to
+35°C (14°F to 95°F)
⚫
Maximum rate of temperature change: 20°C (36°F) per
hour, 5°C (9°F) per 15 minutes
NOTE
The highest operating temperature varies depending on the
server configuration. For details, see A.3 Operating Temperature
Limitations.
Relative humidity (RH,
non-condensing)
⚫
Operating humidity: 8% to 90%
⚫
Storage humidity (within three months): 8% to 85%
⚫
Storage humidity (within six months): 8% to 80%
⚫
Storage humidity (within one year): 20% to 75%
⚫
Maximum change rate: 20%/h
Air volume
≥ 196 cubic feet per minute (CFM)
Operating altitude
≤3050m
⚫
When the server configuration complies with ASHRAE
Classes A1 and A2 and the altitude is above 900 m
(2952.76 ft), the highest operating temperature
decreases by 1°C (1.8°F) for every increase of 300 m
(984.25 ft).
⚫
When the configuration complies with ASHRAE Class
A3 standards and the altitude is above 900 m (2952.76
ft.), the highest operating temperature decreases by
1°C (1.8°F) for every increase of 175 m (574.14 ft.).
⚫
When the server configuration complies with ASHRAE
Class A4 and the altitude is above 900 m (2952.76 ft),
the highest operating temperature decreases by 1°C
(1.8°F) for every increase of 125 m (410.1 ft).