2. It is recommended that the shortest length cable
possible be used to reach between the boilers. Do
not run unprotected cables across the floor or
where they will become wet or damaged. Do not
run communication cables parallel with, or close to
or against, high voltage (120 volt or greater)
wiring. Raypak recommends that the total maxi-
mum length of each set of communication bus
cables not exceed 200 feet.
3. Route the FT_BUS wires from the front along the
top rails and out the back of the cabinets (as
shown in Fig. 14).
4. Connect the FT_BUS wires to the PIM by pressing
down on the slots with a small screwdriver and
then inserting the wires into the holes. See Fig.
18.
Fig. 17: XFyre Cascade System Wiring
Fig. 18: FT_BUS Wire Connection
23