2-5-4. Connection of communication terminals
The communication port of this inverter is standard RS485 port.
With the following wiring methods, you can build up control system of one-host-one-slave or one-host-multi-slaves. Also,
the superior device (PC or PLC) can realize the functions such as real time monitor inverter, remote control, highly auto-
mated motion control.
Connection of inverter RS485 port and superior device:
Fig. 2-9 RS485-(RS485/232)-RS232 cable connection
Many inverters can be connected together through RS485, the PLC(or PC) is the host device, as shown in Fig.2-10;
Also, you can select one inveter as host and the other inverters are slaves, as shown in Fig.2-11.The more inverters are
connected, the communication system will be interfered seriously, the following wiring is recommended.
Fig. 2-10 Connection of PLC and inverters
(Inverters and motors are all grounded well)
Fig. 2-11 Connection of several inverters
Shield
cable
Inverter
RS485/RS232 converter
Terminal
Name
5V power +
+5V
Send data
TXD
Receive data
RXD
5V power -
GND
Terminal
Name
A
Signal -
B
Terminal
Name
Signal -
A
B
Superior device
RS232(DB9)
Signal
Pin
PE
Cover
RXD
2
TXD
3
GND
5
DTR
4
DSR
6
RI
9
CD
1
RTS
7
CTS
8