V5 series inverter
37
P1.09
Max setting of CI
P1.07 ~10.00V
0.01V
10.00V
○
P1.10
Frequency of the
max setting of CI
0.00~highest frequency
0.01Hz
50.00Hz
○
P1.11
Max
input
pulse
frequency
of
PULSE
0.1~20.0K
0.1K
10.0K
○
P1.12
Min
setting
of
PULSE
0.0~P1.14
(Max setting of PULSE)
0.1K
0.1K
○
P1.13
Frequency of the
min
setting
of
PULSE
0.00~highest frequency
0.01Hz
0.00Hz
○
P1.14
Max
setting
of
PULSE
P1.12 (Min setting of PULSE) ~ P1.11
(Max input frequency)
0.1K
10.0K
○
P1.15
Frequency of the
max
setting
of
PULSE
0.00~highest frequency
0.01Hz
50.00Hz
○
P1.16
Input mode of CI
0: 4~20mA
1: 0~10V
-
0
○
3. Starting and Braking Prameters (Group P2)
Group P2: Starting and Braking Prameters
Parameter
Name
Range
Minmum
unit
Factory setting
Change
P2.00
Starting mode
0: Start from the starting
frequency
1: Brake first and then start
from the starting frequency
2: detect current speed then
startup
1
0
×
P2.01
Starting frequency
0.20~20.00Hz
0.01Hz
0.50Hz
○
P2.02
Holding time of starting
frequency
0.0~30.0s
0.1s
0.0s
○
P2.03
DC brake current when
startup
0.0~80.0%
0.1%
0%
○
P2.04
DC brake time when startup
0.0~60.0s
0.1s
0.0s
○
P2.05
Stopping mode
0: Decelerate
1: Free stop
2: Dece DC brake
1
0
×
P2.06
DC brake startup frequency
when stop
0.0~15.00Hz
0.0Hz
3.00Hz
○
P2.07
DC brake time when stop
0.0~60.0s
0.1s
0.0s
○
P2.08
DC brake current when stop
0.0~80.0%
0.1%
0.0%
○