V5 series inverter
44
101: frequency reach signal
(FAR)
102: frequency level detect
signal (FDT1)
103: frequency level detect
signal (FDT2)
104: overload pre-alarm
(OL)
105: inverter under voltage
blockade and stop (LU)
106: external error stop
(EXT)
107:
output
frequency
reach upper limit (FH)
108:
output
frequency
reach lower limit (FL)
109: inverter zero-speed
running
100: simple PLC running is
completed
111: PLC complete one
period running
112: reach the setting count
value
113: reach the middle count
value
114: inverter running prep-
aration (RDY)
115: inverter error
116: run with startup fre-
quency
117: DC brake when star-
tup
118: brake when stop
119:
swing
frequency
up/down limit
120: reach the preset run-
ning time
P4.21
DO max pulse output
frequency
0.1K~20.0K (Max: 20KHz)
0.1KHz
10.0KHz
○
P4.22
preset counting value
arrived
P4.23~9999
1
0
○
P4.23
Mid counting value ar-
rived
0~P4.22
1
0
○
P4.24
Overload pre-alarm de-
tection level
20%~200%
1
130%
○
P4.25
Delay time of over load
pre-alarm
0.0~20.0s
0.1s
5.0s
○