V5 series inverter
63
Seven kinds of Acc/Dec time can be defined, and the inverter’s Acc/Dec time 1~7 can be selected by different combination of
control terminals. Please refer to the introductions of P4.00~P4.05 for the definitions of terminals used to select Acc/Dec time,
also, you can refer to Acc/Dec time defined in P0.17 and P0.18.
P3.26
Multi-frequency 1
Range: lower limit of frequency~upper limit of frequency
5.00Hz
P3.27
Multi-frequency 2
Range: lower limit of frequency~upper limit of frequency
10.00Hz
P3.28
Multi-frequency 3
Range: lower limit of frequency~upper limit of frequency
20.00Hz
P3.29
Multi-frequency 4
Range: lower limit of frequency~upper limit of frequency
30.00Hz
P3.30
Multi-frequency 5
Range: lower limit of frequency~upper limit of frequency
40.00Hz
P3.31
Multi-frequency 6
Range: lower limit of frequency~upper limit of frequency
45.00Hz
P3.32
Multi-frequency 7
Range: lower limit of frequency~upper limit of frequency
50.00Hz
These frequencies will be used in multi-step speed operation and simple PLC operation, please refer to the introductions of
P4.00~P4.05 and P8.
P3.33
Jump frequency 1
Range: 0.00
-
500.00Hz
0.00Hz
P3.34
Range of jump frequency 1
Range: 0.00
-
30.00Hz
0.00Hz
P3.35
Jump frequency 2
Range: 0.00
-
500.00Hz
0.00Hz
P3.36
Range of jump frequency 2
Range: 0.00
-
30.00Hz
0.00Hz
P3.37
Jump frequency 3
Range: 0.00
-
500.00Hz
0.00Hz
P3.38
Range of jump frequency 3
Range: 0.00
-
30.00Hz
0.00Hz
P3.33~P3.38 define the functions that will avoid resonant point of mechnical load.The frequency of the inverter can do
jump operation near some jump frequency point, as shown in Fig. 6-15, you can define three ranges of jump frequency at
most.
Fig.4-15 Jump frequency and range
P3.39
Set running time
Range: 0~65.535K hour
0.000K
P3.40
Accumulate running time
Range: 0~65.535K hour
*
If accumulated running time reach the setting time (P3.39), the inverter will output signal, refer to function P4.08~P4.09.
P3.40 refers to the accumulating running time from out of factory till now.
P3.41
Display parameters selection 1
Range: 0000~FFFF
0000
P3.41 uses the 4 bits of this parameter (hex value) to control the displaying of b-09~b-24. Please transform the parameter
to binary value when using. Each binary bit controls the displaying of one monitor parameter b. See Fig 4-16.
P3.41 binary value:
Fig.4
-
16 Display parameters selection 1
b-09 ~ b-12
b-13 ~ b-16
b-17 ~ b-20
b-21 ~ b-24