V5 series inverter
64
P3.42
Display parameters selection 2
Range: 0000~FFFF
0000
P3.42 uses the 4 bits of this parameter (hex value) to control the displaying of b-25~b-40. Please transform the parameter
to binary value when using. Each binary bit controls the displaying of one monitor parameter b. See Fig4-17.
P3.42 binary value:
Fig.4
-
17 Display parameters selection 2
P3.43
Display parameters selection 3
Range: 0000~4040
0001
Ten bit, lowest bit: used to set stop status
Thousand bit, hundred bit: used to set running status
Example: display current value in running status and display DC bus voltage value in stop mode, please set P3.43=0304.
You can also press the key to view other monitor parameters.
P3.44
Display coefficient without unit
Range: 0.1~60.0
1.0
Display value of b-14 = Output frequency of inverter×P3.44 (proportion)
P3.45
JOG/REV switching
Range: 0, 1
0
P3.45 is used to select the working mode of JOG/REV key on the operate panel:
0: JOG
1: REV
4-2-5. Function parameters of terminal (Group P4)
P4.00
Function selection of input terminal X1
Range: 0~37
1
P4.01
Function selection of input terminal X2
Range: 0~37
2
P4.02
Function selection of input terminal X3
Range: 0~37
3
P4.03
Function selection of input terminal X4
Range: 0~37
10
P4.04
Function selection of input terminal X5
Range: 0~37
17
P4.05
Function selection of input terminal X6
Range: 0~37
18
P4.06
Function selection of input terminal X7
Range: 0~37
0
P4.07
Function selection of input terminal X8
Range: 0~37
0
Multi-function input terminals X1~X8 support various functions. You can define the function of X1~X8 by setting
the value of P4.00~P4.07, refer to Table 4-1. Among these terminals, X7 corresponds to FWD and X8 corresponds to
REV.
Table 4-1 Multi-function selection
Setting
Functions
Setting
Functions
0
Control terminals are idle
19
Frequency setting channel 1
b-25 ~ b-28
b-29 ~ b-32
b-33 ~ b-36
b-37 ~ b-40
0000
0000
0000
0000