V5 series inverter
71
20:
Reach the setting running time.
When the accumulating running time
(
P3.40
)
arrive the setting time (P3.39), an
indication signal will be output.
P4.12
Detecting range of frequency arrive (FAR)
Range: 0.00~50.00Hz
5.00Hz
This parameter is the additional definition of No. 1 function in Table 4-6. As shown in Fig.4-26, when the output frequency
of inverter is in the detecting range of setting frequency, pulse signal will be output.
Fig 4-26 Frequency arriving signal
P4.13
FDT1 (frequency level) voltage
Range: 0.00~upper limit of frequency
10.00Hz
P4.14
FDT1 lag
Range: 0.00~50.00Hz
1.00Hz
P4.15
FDT2 (frequency level) voltage
Range: 0.00~upper limit of frequency
10.00Hz
P4.16
FDT2 lag
Range: 0.00~50.00Hz
1.00Hz
P4.13~P4.14 is the additional definition of No.2 function in Table.4-6, P4.15~P4.16 is the additional definition of No.3
function in Table.4-6, their using method are the same. The following takes P4.13~P4.14 as an example to introduce.When
the output frequency is over one frequency(FDT1 voltage), indication signal will be output until the output frequency de-
creasing below one frequency of FDT1(FDT1 voltage
-
FDT1 lag), as shown in Fig. 4-27.
Fig.4-27 FDT level
P4.17
Analog output selection (AO)
Range: 0~7
0
P4.18
Analog output gain (AO)
Range: 0.50~2.00
1.00
Table 4-7 Output terminals
No.
Function
Range
0
Output frequency
0~upper limit frequency
1
Output current
0~2 × rated current
2
Output voltage
0~1.2 × rated voltage of load motor
3
Bus voltage
0~800V
4
PID setting
0~10V
5
PID feedback
0~10V
6
VI
0~10V
7
CI
0~10V/4~20mA