S5
Access object numbers
16 bits constant or single word register
S6
Local object address
Local coil
3. Suitable soft component
*Note: D includes D, HD; TD includes TD, HTD; CD includes CD, HCD, HSCD, HSD; DM
includes DM, DHM; DS includes DS, DHS.
M includes M, HM; S includes S, HS; T includes T, HT; C includes C, HC.
Intruction
BIT_WRITE
K1
K3
K0
K8
X0
M0
S1·
S2·
S3·
S4·
S5·
K2
S6.
Function: write the local coil M0~M7 to station no.3 Y0~Y7 in ID1 network.
1-2-3
.
Read register [REG_READ]
1. Instruction explanation
Read the target register to local register.
Read register [REG_READ]
Execution
conditoin
Edge trigger
Suitable
model
XD3, XDM, XD5
Hardware
V3.2 and up
Software
V3.2 and up
2. Operand
Operand
Function
Type
S1
Target net ID
16 bits constant or single word register
S2
Target station number
16 bits constant or single word register
S3
Target object type (refer to chapter 16 bits constant or single word register
Operand
System
X
Y
M
*
S
*
T
*
C
*
Dn.m
S6
● ●
●
●
●
●
Bit
Operand
System
Constant Module
D
*
FD
TD
*
CD
*
DX
DY
DM
*
DS
*
K /H
ID
QD
S1
●
●
●
●
●
S2
●
●
●
●
●
S3
●
●
●
●
●
S4
●
●
●
●
●
S5
●
●
●
●
●
Word