The present position is 2000, it needs 8000 pulse numbers to get the target position of 10000
pulse numbers in incremental mode.
◆
the program in incremental mode
When SM2 is ON, send the pulse numbers, speed, acceleration deceleration time to the related
registers.
Servo is enable, M0 is ffrom OFF to ON, it runs incremental motion instruction MOTO.
M1 is from OFF to ON, send absolute position to the related register.
M2 is from OFF to ON, send the new speed to the related register.
Running flag SM2001 is reset after the pulse sending is completed, reset M0, M1, M2.
SM2
DMOV
K8000
HD0
DMOV
K5000
HD2
DMOV
K50
HD4
HD0
HD2
HD4
MOTO
K1
M0
DMOV
K20000
SD2030
DMOV
K6000
SD2032
M1
M2
SM2001
RST
M0
RST
M1
RST
M2