background image

       

Extension ED module                           

                                    XD-2AD2DA-A-ED

 

               

             

Fast manual 

Thanks  for  purchasing  XINJE  XD  series  PLC  and  extension  module.  This  manual  will 
introduce the electric features and using method of XD series extension ED module. Please 
read this manual carefully before using the products, make sure the wiring operation is safe.   

       

Features of analog extension module   

        XD-2AD2DA-A-ED 

 

2 channels analog input: current input mode, 0~20mA or 4~20mA. 

 

2 channels analog output: current output mode, 0~20mA or 4~20mA. 

 

12-bit high precision analog input, 10-bit high precision analog output. 

 

As the special function ED module of XD, XD series PLC can connect 1 XD-

2AD2DA-A-ED module. 
 

Safety precautions                                                                   

 

Control system design attentions 

 

     

Dangerous!

   

 

Make  sure  design  the  safety  circuit,  to  ensure  that  the  control  system  can  still  work 

safety when the external power supply cut off or PLC broken.   

 

Make sure set emergency braking circuit, protection circuit, interlock circuit of forward-

reverse running in PLC external circuit and upper-lower limit switch to prevent from 

machine damage. 

 

In order to make the equipment safe operation, please design external protection circuit 

for important output signal. 

 

PLC CPU will close all the output when detecting the system error; the output will lose 

control when the PLC circuit has problem. Please design suitable external control circuit 

to ensure the device working normally. 

 

If the PLC relay or transistor unit is broken, the output cannot be ON or OFF. 

 

The PLC is designed for indoor environment, the lightning protection must be installed 

in the power supply system to avoid PLC and other device damage. 

 

Installation and wiring attentions 

 

 

   

Dangerous!

   

 

Do  not  use  the  PLC  in  the  following  environment:  dust,  soot,  corrosive  gases, 

flammable gas, high temperature, condensation, vibration, impact, lightning, fire. 

 

Do not let the metal scrap and wire head drop into the ventilation hole of PLC, otherwise 

it will cause fire or error operation. 

 

Do not cover the ventilation hole of PLC, otherwise it will cause fire, error operation. 

 

The I/O wiring must be fixed enough, otherwise the bad contactor will cause fault. 

 

Attention!

   

 

It can use external power supply for extension module DC24V power. 

 

Please use shield cable for high frequency I/O wiring to avoid interference.   

 

Run and maintenance 

       

Dangerous!

   

 

Please connect all the cable include PLC, extension module and BD board after shutting 

down the power supply. 

 

Please operate as the manual for online operation, forced output, RUN, STOP.   

 

Attention!

   

 

Please discard the product as industrial waste. 

 

Make sure cut off the power supply when installing or uninstalling the extension card.   

 

Product information                                                                             

 

 

 

Naming rule 

XD– 2 AD 2 DA - A - ED 

         

 

   

   

       

       

           

① 

Product series            XD: XD series extension module 

② 

Analog input channel: 2: 2 channels 

③ 

Analog input              AD: analog input 

④ 

Analog output channel: 2: 2 channels   

⑤ 

Analog output            DA: analog output 

⑥ 

I/O type                      A: current type for input and output 

⑦ 

Module type                ED: left extension ED module 

 

Basic parameters 

XD series PLC can connect 1 extension ED module, the type is not limited. 

 

Table 1: analog extension module XD-2AD2DA-A-ED general specifications 

Item   

Specifications   

Using environment 

No corrosive gas 

Environment temperature 

0

~60

 

Storage temperature 

-20~70

 

Environment humidity 

5~95%RH 

Storage humidity 

5~95%RH 

Installation   

Fix with  M3 screw or install  on the rail DIN46277(width 

35mm) 

 

的导轨上

 

Dimension   

100.0mm×18.0mm×90.0mm 

Table 2: analog extension module XD-2AD2DA-A-ED I/O precision 

Item   

Analog current input (mA) 

Analog current output (mA) 

Analog input 

range   

0~20, 4~20mA 

— 

Max input range   

0~40mA 

— 

Analog output 

range   

— 

0~20, 4~20mA 

External load resistor is less than 

500Ω 

Digital input 

range   

— 

10-bit binary number (0~1023) 

Digital output 

range   

12-bit binary number 

(0~4095) 

Resolution   

1/4095(12Bit) 

1/1023(10Bit) 

integrated 

precision   

                                                      1% 

Transformation 

speed 

2ms/1 channel 

2ms/1 channel 

Power supply for 

analog   

DC24V±10%, 150mA 

Table 3: analog extension module XD-2AD2DA-A-ED AD transformation diagram 

The relationship between analog input and transformed digital value 

0~20mA analog input 

4~20mA analog input 

20mA

+4095

0

analog

di

gi

t

al

 

20mA

4mA

+4095

0

analog

di

gi

t

al

 

 
 
 

The relationship between analog output and digital input   

0~20mA analog output

 

4~20mA analog output

 

20mA

+1023

0

an

al

o

g

digital

 

20mA

4mA

+1023

0

an

al

o

g

digital

 

Note: when the input data is over K1023, DA transformed analog output will keep 20mA. 
 

Product appearance                                                                                                 

Here listed I/O terminal configurations of XD series extension module XD-2AD2DA-A-ED. 

 

Product structure 

 

Each part name:   

Name   

Function   

Indicator 

light 

PWR 

The LED lights when the ED module has power supply   

COM 

The  LED  lights  when  the  ED  module  communication 

port works well   

ERR 

The LED lights when the ED module has error   

Wiring 

terminal 

24V 

ED module external power supply 24V +   

0V 

ED module external power supply 24V - 

AI0 

Channel 1 analog input 

AI1 

Channel 2 analog input   

CI0 

AI0, AI1 ground 

AO0 

Channel 1 analog output 

AO1 

Channel 2 analog output 

CO0 

AO0, AO1 ground 

 

Product dimension and installation                                   

 

Installation 

Do not install the module in below environment:   

 

Direct sunlight 

 

Environment temperature out of range 0-50

 

 

Environment humidity out of range 35%-85% RH 

 

Condensation as severe changes in temperature 

 

Corrosive gas and flammable gas 

 

Dust, iron filing, salt, fume 

 

Vibration and impact 

 

Spray oil, water and medicine 

 

Strong magnetic field and strong electric field 

 

 

XD series extension ED module can be installed in com3 port of XD series PLC.   

Note: please cut off the power before operation!

                     

 

 

Product dimension 

  (Unit: mm)

 

XD series extension ED module dimension is shown as below:

 

 

 

Electric design reference                                                                   

 

I/O address 

XD series extension ED module will not occupy I/O unit, the transformed value is stored in 
PLC register. The following is the PLC register corresponding to each channel. 

 

Channel   

AD signal 

0CH 

ID30000 

1CH 

ID30001 

Channel   

DA signal 

0CH 

QD30000 

1CH 

QD30001 

 

Working mode setting 

 

 

TYPE:XDM-32T4-E

DATE:20120701

SN:201207011525

Xinje Electronic Co.,Ltd

COM3

PWR

COM

ERR