Summary of Contents for XMP-18 Series

Page 1: ...XINJE XP XMP 18 series Integral industrial controller Operating manual ...

Page 2: ...e r i e s O p e r a t i n gm a n u a l V 1 0 Catalog Preface Safety Notes Summarization Input output specification and exterior layout PLC Function and Application HMI Function and Application Extension Ability 1 2 3 4 5 ...

Page 3: ...rk normally in the condition of be transported kept and installed correctly also please operate and maintain them according to the recommendation Xinje Electronic Co Ltd Copyright reserved Without exact paper file allowance copy translate or using the manual is not allowed Disobey this people should take the responsibility of loss We reserve all the right of expansions and their design patent Duty...

Page 4: ...ecs and circuit 19 2 3 Transistor output specs and circuit 21 3 PLC FUNCTION AND APPLICATION 23 3 1 PLC instruction 23 3 2 soft component range 24 3 3 Set up a project 28 3 4 communication function 31 4 HMI FUNCTION AND APPLICATION 35 4 1 HMI function introduction 35 4 2 Build a project 36 5 THE EXTENSION ABILITY OF XP XMP 39 5 1 extend BD board 39 5 2 extend MA model 42 5 3 Other extension 45 Cat...

Page 5: ...uct characteristics spec explanation using method etc n This manual contains product summarization exterior layout PLC program and exterior extension Ø Summarization introduce the product characteristics specs dimension installation Ø Exterior layout introduce the product power spec in out layout Ø PLC program introduce how to program in PLC Ø HMI picture introduce how to edit picture in OP Ø Exte...

Page 6: ...en with pen screwdriver or other sharp tools it may cause screen break or error For installing the product tighten the screws to avoid loosing Transport install store assemble and maintain the product accurately to avoid breaking Confirm the power voltage and wire connection before turn on the power in order to avoid breaking Do not touch the connection point to avoid getting an electric shock Do ...

Page 7: ... can extend BD board to realize analog quantity in out control Easy edit of the HMI picture rich function u LCD display 192 64 pixel 3 7 inch LCD useful life can reach 0 5 million hours u 26 function keys can be redefined by user u Sensitive and accurate key press u Multifunctional download port HMI and PLC use one download cable u Waterproof level is IP20 u Small structure space saving u Simple a...

Page 8: ...ries 3 In out points 18 Input 10 points output 8 points 4 Output Type R Relay output T Transistor output RT Relay Transistor output Notice XMP series exclude XMP2 32 series products in this manual About these products please refer to Integral Controller Manual XMP2 32 Type Name ...

Page 9: ...0V between signal and ground Operating temperature 0 50 Storage temperature 10 60 Environment temperature 20 85 No dew Endurable quiver 10 25Hz X Y Z direction for 30 minutes Anti jamming Voltage Noise 1000Vp p Air No causticity gas Surrounding Protection According to IP20 Cooling mode Natural wind Dimension 172 0 121 0 56 5 Configuration Panel open aperture dimension 164 0 113 0 Download port RS ...

Page 10: ... Set time 0 01 327 67 seconds 1mS timer Set time 0 001 32 767 seconds Points 48 640 640 Counter C Specs 16 bits counter set value K0 32767 32 bits counter set value 2147483648 2147483647 Data Register D 288 words 2612 words 9024 words Specs Item XP series XMP series Type Kelly Blue LCD Screen dimension 3 7 inch Useful life Over 20000 hours 25 24hours operating Display area 192 64 Contrast Regulati...

Page 11: ...rnal interrupt Setting of time scan space 0 99mS Password protection 6 bits ASCII Self diagnose function Power on self diagnose Monitor timer grammar check Note The user program capacity is referred to the capacity under secret downloading mode 1 3 Parts explanation Configuration 5 6 7 8 4 3 2 1 0 1 2 3 4 5 9 8 7 6 Number key Screen area Function key ...

Page 12: ...in Function Pin2 RXD Pin3 TXD Pin5 GND Pin7 RTS Xinje provides special program cable to download the PLC program or HMI program You also can make the cable by yourself Please see the pin connection between PC and the port MODE XP3 1 8 R SN 2 0 0 6 0 5 0 2 1 1 8 DATE 2 0 0 6 0 5 1 0 无锡市信捷科技电子有限公司 Points connect with BD board Program port Power supply RS 485 Com port Output points Input points In ou...

Page 13: ...S 7 CTS Communication port A and B is a RS 485 com port This port is used to connect other devices Please refer to paragraph 3 4 for details 1 4 Outline dimension Unit mm Communication port Outline dimension 1 2 1 1 6 2 1 1 1 5 6 5 1 7 2 6 7 8 9 5 4 3 2 1 0 1 2 3 4 8 7 6 5 ...

Page 14: ...16 Unit mm Installation dimension 1 6 4 1 1 3 ...

Page 15: ...ld be NPN open collector D Cp o w e r D C 2 4 V p o w e rs u p p l y R 3 R 4 R 2 R 1 X 7 X 0 C O M 5 V R 5 R 6 L E D I 7 m A s e n s o r s u p p l y Input signal s voltage DC24V 10 Input signal s current 7mA DC24V Input ON current Above 4 5mA Input OFF current Below 1 5mA Input response time About 10ms Input signal s format Contact input or NPN open collector transistor Circuit insulation Photo el...

Page 16: ...pler the second loop has C R filter which can prevent wrong action caused by industry noise or input points oscillation As the result there will be a response delay for 10ms to the input points There is digital filter in the input points l Input sensitivity Input current is DC 24V 7mA To make the input reliable the ON current should be above 3 5mA the OFF current should be below 1 5mA Typical conn...

Page 17: ...produces close sound when it is on l Response time The response time is about 10ms transferring the ON or OFF signal from relay output coil to the output connection l Output current Output current is 3A per point to drive resistor load for voltage below AC250V Inductor load is below 80VA AC100V or AC200V and light load is below 100W AC100V or AC200V l Open leakage current There is no leakage curre...

Page 18: ...he product will be broken l For DC inductor load please parallel connect with commutate diode If not connect with the commutate diode the point s life will be decreased greatly Please choose the commutate diode which allow inverse voltage endurance up to 5 10 times of the load s voltage ordinal current exceeds load current l Parallel connect AC inductor load with surge absorber can reduce noise an...

Page 19: ... Maximum current 50mA Maximum pulse frequency 200KHZ Type RT output T output Transistor output point Y2 Y3 Y2 Y7 Power supply Below DC5 30V Circuit insulation Optical coupling insulation Resistor load 0 4A Inductor load 12W DC24V Maximum load Light load 1 5W DC24V Minimum load DC5V 2mA OFF ON Below 0 2ms Repose time ON OFF Below 0 2ms l Output point High speed pulse output Normal transistor output...

Page 20: ...istor is ON l Response time From optical coupler driving or cut to transistor ON or OFF the time is below 0 2ms l Output current The current is 0 4A per point But due to restriction of temperature going up the total current is 0 8A every four points l Open current Less than 0 1mA u s es u i t a b l ef u s ef o rt h el o a d T oa v o i db u r n i n gP L Cb a s i cc i r c u i t D Cp o w e r D C 5 3 ...

Page 21: ...ied instructions and special function instructions Please refer to XC Series PLC Manual paragraph 4 5 6 XP2 XMP2 and XP3 XMP3 have special function instructions please refer to XC Series PLC Operating Manual paragraph 6 Here we only give the port definition and distribution 1 High speed count XP2 XMP2 XP3 XMP3 series Increase mode Pulse direction mode AB phase mode C600C602C604C606C608C610C612C614...

Page 22: ... X5 I0100 I0101 M8051 CHL3 X10 I0200 I0201 M8052 4 Frequency measurement The point is X1 X11 X12 5 Pulse width modulation The point is Y0 Y1 u T type Y0 Y1 available u RT type Y0 Y1 available u R type unavailable 6 Precise timer 32 bit precise timer the timer range is T600 to T618 match with 10 interruption tag 3 2 soft component range XP XMP series soft component ID distribution list is as below ...

Page 23: ... 10ms accumulation T400 T403 1ms not accumulation T Timer T500 T503 1ms accumulation 80 C0 C23 16 bits plus counter C300 C315 32bits plus minus counter C600 C603 vacant C620 C621 vacant C Counter C630 C631 vacant 48 D0 D99 D100 D149 150 For special using D8000 D8029 For special using D8060 D8079 For special using D8120 D8179 For special using D8240 D8249 For special using D8306 D8313 D Data regist...

Page 24: ...20 C598 32 bits forth back counter C600 C619 one phase high speed counter C620 C629 Pulse direction high speed counter C Counter C630 C639 AB phase high speed counter 640 D0 D999 D4000 D4999 D0 D3999 D4000 D7999 2000 8000 D Data register For special using D8000 D8511 D8630 D8729 For special using D8000 D9023 612 1024 FD0 FD127 FD0 FD1535 128 1536 FD FlashROM register For special using FD8000 FD838...

Page 25: ...631 S FD8206 First address of the power failure memory area of S 512 S0 S31 XP2 XMP2 Soft component Area Function Default value Power failure memory area D FD8202 First address of the power failure memory area of D 4000 D4000 D4999 M FD8203 First address of the power failure memory area of M 3000 M3000 M7999 T FD8204 First address of the power failure memory area of T 640 No set C FD8205 First add...

Page 26: ...ED0 ED16383 NOTE Users can set the power failure memory area but the area can not over the soft component area 3 3 Set up a project The PLC program editing software is the same as Xinje XC series Software name is XCPPro The interface of software is as below We take XP3 18R as a example to explain how to set up a project 1 Modify the type Open the software click file change PLC model About the soft...

Page 27: ...mpile the program For program compiling and software operating please refer to XC Series Edit Tool XCP Pro User Manual XP1 XMP1series choose XP1 18 XMP1 18 XP2 XMP2 series choose XP2 18 XMP2 18 XP3 XMP3 series choose XP3 18 XMP3 18 ...

Page 28: ...k to choose these parameters automatically When below window shows connect to PLC succeeded it means the connecting is successful Click OK to continue If the connecting is not successful the window will show communication error Please check the serial port and the cable 2 Download the program After connecting successfully click to download the PLC program If the PLC is running it will pop up the s...

Page 29: ...ation protocol The instructions please refer to XC Series PLC Operating Manual paragraph 6 4 1 and 6 4 2 XP XMP series product have program port DB9 pins port and RS 485 com port A B point Program port can only be used to download PLC program and HMI pictures However RS 485 port can be used to communicate with other devices RS 485 port can be connected with varied devices the communication paramet...

Page 30: ...a bit 8 or 7 bits Stop bit 2 or 1 bits Check Even odd no check The defaulted parameters of the port Station number is 1 baud rate is 19200bps 8 data bit 1 stop bit even check User can set com port parameters Please see below list for details Attention After changing the parameters in Flash register it is need to reboot the XP XMP to make the setting become effective MODE XP3 1 8 R SN 2 0 0 6 0 5 0...

Page 31: ...ion mode station number 255 is free format 1 254 is modbus station number FD8221 Communication format Baud rate data bit stop bit check FD8222 ASC timeout judgment time Unit ms 0 means no timeout waiting FD8223 Reply timeout judgment time Unit ms 0 means no timeout waiting FD8224 Start symbol High 8 bits invalid FD8225 End symbol High 8 bits invalid AB com port FD8226 Free format setting 8 16 bits...

Page 32: ...al 16384 16927 4000 421F Y0 Y1037 octal 18432 18975 4800 4A1F S0 S1023 20480 21503 5000 53FF M8000 M8511 24576 25087 6000 61FF T0 T618 25600 26218 6400 666A C0 C634 27648 28282 6C00 6E7A Register space Modbus address prefix is 4x Word component address Modbus address decimal K Modbus address hex H D0 D7999 0 7999 0 1F3F TD0 TD618 12288 12906 3000 326A CD0 CD634 14336 14970 3800 3A7A D8000 D8511 16...

Page 33: ...sing ENT key press SET key again to cancel the setting and continue modifying the next data register To write the modified value in the register and continue modifying next register After the last register in the screen has been modified it will quit the setting Alarming list key After setting the function of alarming list press this key to jump to the alarming list screen Clear the selected area ...

Page 34: ...36 4 2 Build a project XP XMP series product integrated the function of HMI and PLC when editing the HMI screen use HMI software OP20 The interface of OP20 is shown as below About the software ...

Page 35: ...s the XP XMP is a integrated product of OP and XC the OP will communicate with XC inside the product the communication parameters are defaulted 4 edit the screen After these three steps we can enter screen editing mode For the editing details please refer to OP Series Display User Manual chapter 2 Build a project This window shows all the display type supported by OP software We can select the cor...

Page 36: ...th the note can not open Click file comm port to select the correct com port 2 download Connect the XP XMP DB9 pins com port and PC serial port using download cable Power on the XP XMP click to start downloading If the downloading is completed it will pop up below window Attention 1 Do not cut the power when downloading or you have to download again 2 The downloading cable of downloading OP screen...

Page 37: ... K thermocouple temperature measurement PID adjustment inside XP3 2PT2AD1DA BD 2 channels PT100 temperature measurement 2 channels analog input 1 channel analog output XP3 2AD2PT BD Item Voltage input Temperature input Analog input signal DC0 5V 0 10V Input resistor 300k Ω Platinum resistor Pt100 2 line format Temperature measurement range 100 350 Distinguish ratio 0 15mV 10 16383 0 1 Digital outp...

Page 38: ...t points 2 points Output format NPN collector open transistor output Control precision 0 4 Distinguish ratio 0 1 Integrated precision 0 8 relative max value Convert speed 45ms 2 channels Analog using power DC24V 10 50mA XP3 2PT2AD1DA BD Item Voltage input Temperature input D A output Analog input signal DC0 5V 0 10V input resistor 300kΩ Platinum resistor Pt100 2 lines format Digital input range 10...

Page 39: ...sulation among each channel of PLC I O point 0 point As it is operated via data register it is not restricted by master PLC s standard max control points The installation position of BD board on XP3 XMP3 is as below MODE XP3 1 8 R SN 2 0 0 6 0 5 0 2 1 1 8 DATE 2 0 0 6 0 5 1 0 无锡市信捷科技电子有限公司 The configuration method and using details please refer to BD Board Manual Installation position of BD board ...

Page 40: ... K thermocouple temperature control MA 6PT P 6 channels PT100 temperature control Type Description MA 8X8YR 8 channels digital input 8 channels digital relay output MA 16X 16 channels digital input MA 16YR 16 channels digital relay output MA 16YT 16 channels digital transistor output MA 4DA Item Voltage output Current output DC0 5V 0 10V DC0 20mA 4 20mA Analog output range exterior load resistor 2...

Page 41: ... input type Voltage input Current input Analog input range 0 5V 0 10V 0 20mA 4 20mA Maximum input range DC 18V 0 40mA Digital output range 12 bits binary value 0 4095 Resolution 1 4095 12Bit PID output range 0 K4095 Integrated precision 0 8 Converting speed 20ms per channel Power for analog DC24V 10 100mA Installation Fix up the module with M3 screw or put on DIN46277 rail width 35mm Profile dimen...

Page 42: ...0 1000 Digital output range 0 4095 12 bits with sign binary Precision 1 Integrated precision 1 Conversion speed 20ms 1 channel Power supply for analog DC24V 10 50mA Installation Use M3 screw or fix on DIN46277 width 35mm rail Profile dimension 63mm 102mm 73 3mm Item Description Analog input signal Pt100 Pt hot resistance Measure temperature range 100 350 Digital output range Full scale 4095 12 bit...

Page 43: ... G N D A O XP XMP MA station No 1 MA station No 16 The details and using method please refer to MA Model Manual 5 3 Other extension Besides BD board and MA model XP XMP series product can extend other devices which support RS 485 and Modbus protocol XP XMP can extend 32 devices via RS 485 com port such as PLC meter printer inverter HMI etc The connection figure is as below 5 6 7 8 4 3 2 1 0 1 2 3 ...