High speed processing 

function   

High speed count

pulse output

external interrupt 

Setting of time scan space 

0~99mS 

Password protection 

6 bits ASCII 

Self diagnose function 

Power on self-diagnose

Monitor timer

grammar check 

 

1-2-4 Product type 

 

 

XMP-32 series 

Relay output 

Transistor output 

XMP2-32R-E 

XMP2-32T-E 

XMP2-32R-C 

XMP3-32T-C 

 

NOTE: 

-E means the power supply is AC220V 

-C means the power supply is DC24V 

 

 

 

 

 

 

1-2-5 Name rule 

 

 

 

                                                     

1                2                    3            4 

                                                 

                                        1: series name                      XMP 

                                        2: PLC type                          2: XC2 series 

                                        3: I/O points                        32: input 16/output 16 points 

                                        4: output type                          R: relay output 

                                                                                        T: transistor output 

 

 

 

 

Summary of Contents for XMP2-32 series

Page 1: ...XINJE XMP2 32 series Integral industrial controller Operating manual Xinje Electronic Co Ltd ...

Page 2: ... 9 1 4 Outline dimension 9 2 In out specs and exterior layout 10 2 1 Input specs and layout 10 2 2 Output specs and layout 11 3 PLC function and using 13 3 1 PLC instruction 13 3 2 Soft component range 14 3 3 Build a project 16 3 4 Communication function 18 3 4 1 Com port 18 3 4 2 Communication parameters 18 3 4 3 Communication mode 20 4 HMI function and using 21 4 1 HMI function 21 4 2 Build a pr...

Page 3: ......

Page 4: ...pixel 7 inch screen LCD life can reach 0 5 million hours 26 function keys function setting freely sensitive and precise key press Support high speed count high speed pulse external interrupt Mix function designed download port the same cable for downloading HMI and PLC program Waterproof level is IP20 Close construction save the space of electric control cabinet Simple modern and decent appearance...

Page 5: ...s 100mS timer Set time 0 1 3276 7 seconds 10mS timer Set time 0 01 327 67 seconds 1mS timer Set time 0 001 32 767 seconds Points 640 Counter C Specs 16 bits counter set value K0 32767 32 bits counter set value 2147483648 2147483647 Data Register D 2612 words Flash ROM Register FD 512 words Type TFT 256 colour LCD Screen dimension 7 inch Use life Over 50000 hours 25 24 hours operating Display area ...

Page 6: ...self diagnose Monitor timer grammar check 1 2 4 Product type XMP 32 series Relay output Transistor output XMP2 32R E XMP2 32T E XMP2 32R C XMP3 32T C NOTE E means the power supply is AC220V C means the power supply is DC24V 1 2 5 Name rule 1 2 3 4 1 series name XMP 2 PLC type 2 XC2 series 3 I O points 32 input 16 output 16 points 4 output type R relay output T transistor output ...

Page 7: ...1 3 Part name Display and touch area Number key Function key Power point Product label Input point Output point Com port Download port USB CJ45 port ...

Page 8: ... with slave device Cable connection figure Attention 1 Do not cut the power when downloading or you have to download again 2 The cable of downloading HMI program is the same as the downloading PLC program 3 Do not download when XCPPro and Touchwin software are both running 4 RS 232 download port is only used to download do not use it in other way Pin1 A Pin9 B Pin6 PRT when HMI connecting with sla...

Page 9: ...nd HMI Pin2 RXD Pin3 TXD Pin5 GND 1 3 4 Port A and B The port is RS 485 standard is used to connect meter inverter extension model etc Attention A B port and RS 232 com port are the same port can not be used at the same time 1 4 Outline dimension Outline dimension mm ...

Page 10: ...gure Input signal voltage DC24V 10 Input signal current 7mA DC24V Input ON current Above 4 5mA Input OFF current Below 1 5mA Input response time About 10ms Input signal format Point input or NPN collector open transistor Circuit insulation Photo electricity coupling insulation Input action display LED is ON when input ON ...

Page 11: ...Circuit insulation Machine insulation Action indication LED light Resistor load 3A Induction load 80VA Max load Light load 100W Open creepage current No Minimum load DC5V 2mA OFF ON 10ms Response time ON OFF 10ms Transistor output Interior power Below DC5 30V Circuit insulation Optical coupling insulation Action indication LED light Resistor load 0 8A Induction load 12w DC24V Max load Light load 1...

Page 12: ...s ee v e r y4p o i n t s s u p p l y u Transistor output connection u s es u i t a b l ef u s ef o rt h el o a d T oa v o i db u r n i n gP L Cb a s i cc i r c u i t D Cp o w e r D C 5 3 0 V L o a d L o a d L o a d L o a d 1 A c i r c u i t d r i v e p h o t o e l e c t r i c i t y Y 4 Y 5 Y 6 Y 7 s u p p l y Output point arrangement Open creepage current 0 1 mA Minimum load DC5V 2mA OFF ON 0 2ms ...

Page 13: ... your information 1 high speed count 1 Increment mode 5 channels 2 Pulse direction mode 2 channels 3 AB phase mode 2 channel 2 High speed pulse output a T type Y0 Y1 available the highest frequency is 200KHz b R type unavailable Channel Input Counter Highest frequency CHL1 X0 C600 80KHZ CHL2 X1 C602 80KHZ CHL3 X3 C604 10KHZ CHL4 X6 C606 10KHZ CHL5 X7 C608 10KHZ Channel Input Pulse Direction Counte...

Page 14: ...r the timer range is T600 to T618 match with 10 interruption tag 3 2 Soft component range Soft component Name Range Point X Input point X000 X017 octal 16 Y Output point Y000 Y017 octal 16 M0 M2999 M3000 M7999 8000 M Auxiliary relay M8000 M8767 768 S Process S0 S511 S512 M1023 1024 T0 T99 100ms not accumulation T100 T199 100ms accumulation T200 T299 10ms not accumulation T300 T399 10ms accumulatio...

Page 15: ... power is cut No battery 3 The serial number of input coil and output relay are octal data other memorizers number are all decimal data 4 There is no I O point connected with exterior device can be used as interior relay Soft component power failure area setting Soft component Area Function Default value Power failure memory area D FD8202 First address of the power failure memory area of D 4000 D4...

Page 16: ...which is the same as XC series PLC 1 select the product type Open XCPPro click file change PLC model Select XMP2 32 2 edit the PLC program After selecting the type user can edit the program in the software The editing specs and operating details please refer to XC Series PLC Edit Software XCPPro Manual The interface of software is as below ...

Page 17: ...rrect serial port baud rate and parity or click check to choose these parameters automatically When below window shows connect to PLC succeeded it means the connecting is successful Click OK to continue If the connecting is not successful the window will show communication error Please check the serial port and the cable After connecting successfully click to download the PLC program If the PLC is...

Page 18: ...ave program port DB9 pins port RS 232 com port DB9 pins port and RS 485 com port A and B point Program port can only be used to download PLC program and HMI pictures However RS 232 and RS 485 com port can be used to communicate with other devices The communication parameters baud rate data bit etc can be set via software RS 485 com port point A means signal point B means signal Attention RS 485 an...

Page 19: ...ter changing the parameters in Flash register it is need to reboot the XMP to make the setting become effective Number Function Description FD8220 Communication mode station number 255 is free format 1 254 is modbus station number FD8221 Communication format Baud rate data bit stop bit check FD8222 ASC timeout judgment time Unit ms 0 means no timeout waiting FD8223 Reply timeout judgment time Unit...

Page 20: ... it can only respond to other master devices The defaulted status of XMP is Modbus slave mode The internal soft unit s numbers of XMP are corresponded with Modbus station address numbers please see the following table Coil space Modbus address prefix is 0x Bit component address Modbus address decimal K Modbus address hex H M0 M7999 0 7999 0 1F3F X0 X1037 octal 16384 16927 4000 421F Y0 Y1037 octal ...

Page 21: ...communicating in free format mode FD8220 should be 255 3B4 HMI function and using 4 1 HMI function The HMI part of XMP2 32 series product is integrated with MP 760T touch screen The faceplate key presses are as below Key Function Running the program LED indication light Stop running the program LED indication light Whatever the mode of the display is in it will return to original system screen onc...

Page 22: ...lear the selected area when modifying the register data Set the positive or negative of the data when modifying the register data Number key 0 9 press the key to set the number you want Function key F1 F6 NOTE Besides the function listed in the up table all the keys can be defined as the function of force ON force OFF reverse or momentary ON Please see below picture Open TouchWin software put a bu...

Page 23: ...Build a project Please use Touchwin software Open the software click File New or click to build a new project Choose MP760 T XMP 32 in the panel window Click next choose Xinje XC series for PLC port device ...

Page 24: ...ck next choose Unuse download port for download port device Click next to complete the building The editing interface is as below The software using details please refer to TP Touch Screen Operating Manual ...

Page 25: ...ouchWin screen is the same as downloading PLC program 3 Do not download when XCPPro and TouchWin software are both opened 5 The extension ability 5 1 Summarization XMP2 32 series product can not extend BD board For extending other devices use RS 232 or RS 485 point A and B com port RS 232 com port can connect with computer HMI to monitor the program RS 485 com port can connect with meter inverter ...

Page 26: ...and measure analog quantity The type and specs of MA model are as below Type Function MA 8X8YR 8 channels digital input 8 channels digital output MA 16X 16 channels digital input MA 16YR T 16 channels digital output MA 4DA 4 channels analog output MA 4AD 4 channels analog input MA 8AD A V 8 channels analog input MA 4AD2DA 4 channels analog input 2 channels analog output MA 6TC P 6 channels type K ...

Page 27: ...speed 3ms 1 channel Power of analog quantity DC24V 10 100mA Installation Use M3 screw or fix on DIN46277 rail width 35mm Profile dimension 63mm 102mm 73 3mm MA 8AD A V Item Voltage Current DC0 5V 0 10V DC0 20mA 4 20mA Analog input range exterior load resistor 2KΩ 1MΩ exterior load resistor less than 500Ω Maximum input range 18V 0 40mA Digital output range 12 bits binary numbers Resolution 1 4095 1...

Page 28: ...nput range 0 5V 0 10V 0 20mA 4 20mA Max input range DC 18V 0 40mA Analog output range 0 5V 0 10V exterior load resistor 2KΩ 1MΩ 0 20mA 4 20mA exterior load resistor less than 500Ω Digital input range 10 bits binary number 0 1023 Digital output range 12 bits binary number 0 4095 Resolution 1 4095 12Bit 1 1023 10Bit PID output value 0 K4095 Integrated precision 0 8 Conversion speed 20ms 1 channel 3m...

Page 29: ...R U N P W R S T O P A a a a a aa a a a a a a a a a a a a a a a a a a a a a a a a aa a a a a a a a a a a F 1 F 2 F 3 F 4 F 5 F 6 A L M 7 6 9 8 3 2 5 4 1 0 Integrated precision 1 Conversion speed 20ms 1 channel Power supply for analog DC24V 10 50mA Installation Use M3 screw or fix on DIN46277 width 35mm rail Profile dimension 63mm 102mm 73 3mm Item Description Analog input signal Pt100 Pt hot resist...