1. The gas supply shall have a gas meter & regulator large enough to handle
ALL
of the gas ap-
pliances, such as the furnace, water heater, & ovens in operation at the same time. Add up all
of the Btu/kw/MJ ratings to determine the total load.
2. The gas supply shall have a separate gas meter and gas pressure regulator for each occupant.
Installations in multiple occupancy buildings, (strip malls) shall not share gas meters and regu-
lators with other occupants.
3. Gas hose assemblies with quick disconnects for each oven deck will be installed at each valve.
4. A sediment trap shall be installed downstream of the equipment shutoff valve as close to the
inlet of the appliance as practical atr the tiume of appliance installation. The sediment trap
shall be either a tee fitting with a capped nipple in the bottom outlet as illustrated, and in accor-
dance with ANSI Z223.1-2012 and NFPA 54-2012 National Fuel Gas Code, section 9.6.7.
All installations must conform to local building & mechanical codes.
NOTE
Item # Description
1
1-½ [40] Shut-Off Valve
2
¾ [20] Shut-Off Valve
3
6 [150] Nipple
4
¾ [20] Nipple
5
Reducing Tee
6
Tee
7
Cap
8
Plug
All pipe fittings to be 1-½ [40] minimum
unless noted. NPT & BSP
1
3
2
4
5
6
7
8
3
3
4
NOTE
Do not use Teflon tape on gas line connections as this can possibly cause gas valve
malfunction or plugging of orifices from shreds of tape. Use of Teflon tape may af-
fect warranty.
CAUTION
OVEN GAS REQUIREMENTS