USER MANUAL
- OPTIMA-33 10K / 20K / 30K
www.xmart-ups.com
150805-OPTIMA-33 10K/20K/30K (ENGLISH) - 5
3.- UPS INSTALLATION: SITE PLANNING
SAFETY INSTRUCTIONS
WARNING: Before revising this section you must read and understand very well section 1 of this manual: “GENERAL SAFETY
INSTRUCTIONS”.
WARNINGS, RECOMMENDATIONS AND LIABILITY LIMITATION
REACH AND LIABILITY LIMITATION:
The preparation of the site, wiring and all protection devices must be supplied by end user and it will not
be responsibility neither the UPS distributor nor the UPS technician in charge of the start-up.
The place will be conditioned be end user or electrical contractor and must fulfill with local normative and directives and UPS technical
requirements.
This manual describes minimal conditions and technical requirements with which the site must accomplish.
Directives and requirements described in this manual, do not pretend to substitute in any way local electrical directives or normative.
In some cases, local directives or regulations might be more exigent than UPS technical requirements described by this manual. In that case
end user electrical contractor must be sure to comply with all related local electrical regulations and directives.
WARNING:
Power lines must be protected by protection devices against over current (breakers) or leak currents with capacity and technology
appropriate to effectively accomplish its function. Moreover, installation grounding must be correct.
WARNING:
Install the UPS in well ventilated locations and leave room enough between UPS and close objects and structures
WARNING:
Do not connect to UPS equipments or devices that exceed its capacity, this would overload the UPS.
WARNING:
This product has been designed to be used indoors protected from water, direct sun light, dust and extreme temperature.
WARNING
: Do not put any object on the UPS; do not apply any force over UPS. Do not cover UPS ventilation.
WARNING
: This UPS must be connected to appropriate electrical service according to selected model. Technical specs sticker in the UPS
shows the UPS power ratings. DO NOT connect this UPS to any of its own power outlets, this could damage the unit permanently.
WARNING:
Do not connect AC motor based equipments without a careful sizing of the UPS based on inrush current instead of average current.
Inrush current typical of motor based system could overload this UPS.