background image

 

USER MANUAL

 

Optima Rack 1-3K

 

___________________________________________________________________________________________________________________________________ 

(120217_EN) OPTIMA-RACK 1K-3K

 

  

9

 

First Time:  

CHARGE BATTERIES FOR 6 HOURS BEFORE CONNECTING YOUR EQUIPMENTS TO UPS 

 

 
 
 
 

 

This product leaves factory with battery fully charged, however during transportation and storage it may loose a 

non determined part of its charge; therefore we recommend plugging it to Power Line for 6 hours before using the 
UPS. 

 

Install this unit in any protected environment with a dust free air flow. Also corrosive vapours and conductive 

contaminants must be avoided. Do not use UPS outdoors or where either temperature or humidity exceeds tech 
specs. Install UPS at least 10 inches away from your monitor to avoid magnetic interference. 

 

1.- Plug input AC power cord to an appropriate power outlet with Line-Neutral-Ground contacts.  

 

Some models come with input power-cord with appropriate plug for your country. 

 

3KVA in 120V could come with input terminal block. For 3KVA-120V models input cable to be 

connected to input Terminal Block must be AWG12 or wider (for lengths shorter than 50 feet – 15m). 
Wire size is strongly affected by length and temperature. Input wire must be selected and installed by 
qualified personnel according to local regulations. 

 
2.- First time leave UPS recharging batteries during 6 hours before connecting your devices to the UPS to let 
batteries recover charging level to offer full battery backup time. 
 
3.- Connect your devices to be protected to UPS outlets. Take care to not overload UPS output by connecting 
devices with higher power ratings than UPS power capacity. Laser printers, scanners and copiers frequently have 
two different power ratings: in stand-by power ratings are very low compared with consumption rating during 
operation. If this kind of products will be connected to the UPS operation power rating must be considering to size 
total power consumption to be connected to UPS. 
 
4.- EPO Function: Emergency Power Off function allows to power off UPS outlets when EPO input is open. When 
EPO port is closed EPO function is disable. When EPO function is activated UPS will perform following actions: 
 
a) Power Off all outlets,  
b) Switch to STAND-BY mode, 
c) Acoustic alarm is activated as continuous beep 
d) Warning message Nº 20 is indicated on LCD. 
To disable EPO mode and recovering normal mode contact switch or jumper in EPO port must be closed and UPS 
must be powered On by selecting ON push button. 
 

 
EXTERNAL BATTERIES OPTION 

OPTIMA models with EX mark (like OPTIMA 3K-EX or OPTIMA-RACK 3K-EX) are able to be connected to 
external battery cabinets (EX-BATT) to offer longer backup times. 
This kind of models has internal batteries as other OPTIMA models but they can also be connected at any moment 
to EX-BATT supplied by XMART. 
Special cables to connect EX-BATT to UPS are supplied inside the box of EX-BATT. 

 

 

USER MANUAL

 

Optima Rack 1-3K

 

___________________________________________________________________________________________________________________________________ 

(120217_EN) OPTIMA-RACK 1K-3K

 

  

10

 

 
3.3.- INSTRUCTIONS TO CONNECT EXTERNAL BATTERIES 

1)

 

Place EX-BATT case close to UPS. Only XMART approved EX-BATT can be connected to UPS EX 

series. 

2)

 

Check DC breakers are in OFF position (circuit OPEN)  

3)

 

Connect UPS to first EX-BATT using XMART approved DC cable. 

4)

 

If more than one EX-BATT will be connected, then connect first EX-BATT to second EX-BATT and so 

on in that way to other EX-BATT. 

5)

 

After all EX-BATT are connected, switch to ON position all DC breakers located in EX-BATT. 

 

Important Note:  

It is not recommendable to connect more than 3 external battery packs to the UPS since recharging time could 
be too long. 

 

External Battery Cabinet Characteristics: 

 

Model: EX-BAT-R3 

Total Batteries: 

12 pieces per cabinet: 2 internal packs of 6 batteries 12V-9AH 

Voltage DC: 

82.1Vdc +/- 1% 

Application: 

OPTIMA-Rack 3K “EX” 

 

4. CONFIGURABLE PARAMETERS 

Any configuration modification must be applied with UPS connected to AC line but in OFF or STAND-BY mode. 
This UPS can be configured to work under some different modes. Some important functions can also be 
configured in CONFIGURATION MODE: 
 

a)

 

Normal Mode: Also known as AC MODE. Under this mode UPS works as ONLINE UPS. UPS outlets are 
supplied by AC power generated by UPS inverter circuit offering a clean power to your devices. 

b)

 

ECO Mode: Under this mode UPS works as OFF-LINE UPS. UPS outlets are supplied by AC input 
source. UPS supervises input source to switch to ONLINE mode only when input source is out of range 
This is not a recommendable mode for those critical applications that require ONLINE UPS. 

Default mode set as factory is NORMAL MODE (Online UPS).  
c)

 

Output Voltage: It can be configured to any of 4 available values: 

 

In 120Vac Models: 110Vac, 115Vac, 120Vac, 127Vac,  

 

In 220Vac Models: 208Vac, 220Vac, 230Vac ó 240Vac 

d)

 

Output Frequency: It can be selected to 50Hz or 60Hz. Default configuration allows auto-selection to 
match with frequency of input AC source. 

 
NOTE: When conversion frequency mode is activated UPS power capacity can be reduced. 

 
e) Programmable Outputs: There are 2 group of outlets: 
 

 

Standard Outlets: They works as expected in any UPS. This kind of outlets under battery keep powered until 

batteries reach very low level or up to UPS receives power off command from software. 

 

Programmable Outlets: If programmable outlets function is configured, programmable outlets can be 

powered off by internal timer before UPS detects very low battery level. Most common application for 
programmable outlets is for connecting non critical devices to them so that backup time can be longer for 
those critical devices connected in standard outlets. 

 

Summary of Contents for OPTIMA-RACK 1.5KVA

Page 1: ...care Do not block UPS ventilation WARNING Make sure to connect this unit to proper power line according to selected model The UPS Technical Specs sticker shows power rating information DO NOT connect...

Page 2: ...1 2003 An Uninterruptible Power Systems UPS Part 1 1 General and Safety Requirement for UPS use operator access areas EMC Directives EN62040 2 2006 An Uninterruptible Power Systems UPS Part 2 Electro...

Page 3: ...TON FUNCTIONS ON MUTE a POWER ON Keep selected during 2 seconds or longer b BEEP MUTE In battery mode Keep selected during 5 seconds or longer to Mute acoustic alarm beep Some alarms cannot be muted a...

Page 4: ..._____________________________________________________________________________________________ 120217_EN OPTIMA RACK 1K 3K 8 3 2 RACK UPS INSTALLATION Rack UPS must be installed using L Shape type guid...

Page 5: ...OPTIMA models but they can also be connected at any moment to EX BATT supplied by XMART Special cables to connect EX BATT to UPS are supplied inside the box of EX BATT USER MANUAL Optima Rack 1 3K ___...

Page 6: ...power from batteries There is no dead time transition time is ZERO ms related to switching from normal mode to battery mode since load is always powered from inverter This is main characteristic of a...

Page 7: ...ry charging level 0 25 26 50 51 75 y 76 100 Indicates battery failure Indicates low battery level Input Information Indicates input voltage input frequency and DC battery voltage Vac Input voltage Vdc...

Page 8: ...ts To able or disable programmable outlets function 09 Programmable To configure timer value in minutes for programmable outlets USER MANUAL Optima Rack 1 3K __________________________________________...

Page 9: ...as selected BATTERY MODE When AC input source is out of range Ups goes to battery mode to supply output from taking energy from batteries USER MANUAL Optima Rack 1 3K _________________________________...

Page 10: ...push button is not been selected properly Push ON button during 2 seconds or longer 1 beep s alarm is active and LCD shows Input Line and Neutral are swapped Rotate UPS plug at wall socket to allow c...

Page 11: ...th terms and conditions stipulated herein Transportation expenses are not covered by this limited warranty 3 Warranty is valid only if the original purchasing document issued to original purchaser by...

Page 12: ...ries Step 2 Take out battery kit from UPS Step 3 Replace old batteries using equivalent batteries with same voltage and capacity in AH Follow instructions of 15 3 Step 4 Reconnect batteries assembly b...

Page 13: ...apacidad 1100VA 800W 1700VA 1200W 2250VA 1600W 3400VA 2400W Range Rango Vac 100 load Model 120V 80Vac 150Vac Model 220V 160Vac 300Vac Range Rango Vac 50 load Model 120V 50Vac 150Vac Model 220V 110Vac...

Reviews: