background image

INDEX

 

USER MANUAL - OPTIMA RT10 6K/10K 

 

 

www.xmart-ups.com 

VER.161205-GA2 (ENG)

 

24 

 

5.

 

OPERATION MODES 

 

This is a True On Line Double Conversion UPS and it is designed to offer clean, bump-less and highest quality power to your computer 

related equipment protecting also your valuable data. Power delivered by UPS is 100% sine wave as main line. 

According to AC main service, and how UPS has been configured, it may operate in following modes: 

 

ONLINE NORMAL Mode  

When UPS is off by selecting ON push button in front panel UPS enters into ONLINE NORMAL mode if AC main service is inside acceptable 

input range. Under this mode UPS Inverter powers outputs and the energy is taken from DC voltage coming from AC/DC converter. Batteries 

are charged by AC Line if required. 

 

BATTERY Mode (Also known Inverter Mode) 

If under ONLINE NORMAL mode UPS detects a problem in AC input Line it enters in battery mode. Under this mode UPS takes energy 

from batteries to feed inverter that generates power for the output. There are no transfers neither micro-cuts on UPS output as inverter was 

already working. The only difference is that energy is now coming from batteries instead of rectifier output. Transfer time is actually Zero 

(0ms). UPS also can enter in battery mode when it is turned on without an acceptable AC input. 

 

STATIC BYPASS (INTERNAL BYPASS):

  

This mode can be adopted if UPS configuration allows BYPASS mode. This configuration is done by using configuration menus in LCD. 

Factory preset for 6K and 10K models is BYPASS mode allowed. 

 

Under bypass mode, UPS AC output is feed from UPS AC input. This mode can be adopted by operator by pressing OFF button in front 

panel (if BYAPSS mode is enable) or automatically in case a problem is detected by UPS. When UPS is in bypass mode, in case AC input 

is interrupted, output will be interrupted also and UPS will power off. No battery mode can be adopted from bypass mode. 

 

Bypass mode can be caused by any of below conditions: 

 

1-

 

Bypass mode is adopted, in case ON button has not been activated as soon as UPS detects a valid AC input on its terminals. 

(If bypass mode is not enable, UPS will simply lights its LCD. Outputs will keep powered off)  

2-

 

Bypass mode is adopted as soon as a problem is detected in its internal circuitries. 

3-

 

Bypass mode is also activated in case an external overload is detected in UPS output. It happens when equipment connected 

to UPS output requires a power higher than max. power of the UPS 

 

MAINTENANCE BYPASS:

  

This is the mode adopted when external bypass switch is activated. On this mode output is feed directly from AC input through external 

bypass lines. On Maintenance Bypass mode, UPS can be turned-off for maintenance. 

In OPTIMA models tower type (T09W and T10) there is a maintenance bypass switch (named MBS) located on rear panel. This switch is 

covered by a safety plate. In OPTIMA RT (RT9W and RT10) the MBS must be external.  

 

 

Additionally, this UPS can adopt under operator demand other operation modes as described: 

 

FREQUENCY CONVERSION:

 

 

 

 

      

 

 

 

This UPS offers a very sophisticated function named frequency conversion (CF) that allows UPS to generate power output at determined 

frequency value (50Hz or 60Hz) no matter input frequency value. UPs will be able to generate output at 50Hz even input source is at 60Hz 

or generate 60Hz even if connected to 50Hz source. 

This function can be configured and activated by LCD. Revise configuration section of this manual. 

 

ECO:

  

Under this mode, UPS powers outputs from the AC input. This is a kind of supervised BYPASS mode. As soon as AC input is out of 

acceptable input range for ECO mode (as defined on LCD configuration menus), UPS switch UPS from ECO to ONLINE mode or battery 

mode. Online mode is adopted if input range is acceptable for ONLINE mode. Switching from ECO to other mode takes about 4ms to10ms. 

ECO mode must be activated on LCD according to configuration section of this manual. 

 

IMPORTANT NOTES: 

1.- Under CF mode, UPS will disable BYPASS mode. Since UPS has been configured to generate output with frequency value different to 

input frequency, BYPASS mode is disable to avoid a not acceptable frequency value at output. 

2.- When CF function is activated, maximum power output is de-rated to 60% of maximum nominal capacity. For example, for a 10KVA 

(8KW) model, when CF is activated maximum output is decreased to 6KVA (4.8KW). 

 

 

 

 

 

Summary of Contents for OPTIMA-RT10-10K

Page 1: ...6K 10K www xmart ups com VER 161205 GA2 ENG 1 VER 1612 05 ENGLISH USER MANUAL OPTIMA RT10 6K 10K UPS ONLINE DOUBLE CONVERSION RACK TOWER INSTALLATION OPTIMA RT10 06K 230V OPTIMA RT10 10K 230V ISOTX 06...

Page 2: ...or distributed totally or partially without written approval of XMART XMART can introduce modifications in their products or manuals without further notice XMART is not responsible of mistakes or miss...

Page 3: ...PRODUCT DESCRIPTION 4 INSTALLATION INSTALLATION INDIVIDUAL UPS INSTALLATION PARALLEL UPS 5 OPERATION MODES 6 OPERATION INTERFACE KEYBOARD LCD 7 UPS CONFIGURATION 8 START UP INDIVIDUAL UPS PARALLEL UPS...

Page 4: ...ere are ALWAYS dangerous voltages EVEN the UPS is OFF and unplugged CAUTION There are dangerous voltages in internal DC Capacitors Wait at least 10 minutes after turning off UPS before opening it to a...

Page 5: ...netic field immunity IEC EN 61000 4 8 Level 4 PERFORMANCE UPS Part 3 Methods of operation specifications and test requirement IEC EN 62040 3 IT Equipment SAFETY Part 1 General Requirements IEC EN 6095...

Page 6: ...Ethernet optional card under SNMP protocol This model can be installed in both tower format and inside 19 rack cabinets Rack installation requires some mounting accessories not included with the produ...

Page 7: ...ectrical shock because high DC voltage External battery banks must be revised before connecting them to UPS to confirm their DC voltage is compatible with this UPS DC polarity of the Battery bank must...

Page 8: ...find voltage in input lines of the UPS so that a backfeed failure could represent an electrical shock risk for the operator An effective backfeed design must be able to open automatically all UPS AC...

Page 9: ...in sites exposed to sun light or heat sources Temperature at operation site should never rise over 35 C Batteries life shortens over 25 C Installation site must be dry fresh free of dust fibers and an...

Page 10: ...net 19 RACK MOUNTING Rack UPS must be installed using L Shape type guides for supporting UPS weight Usually this kind of supports is provided with rack cabinets If not UPS distributor can provide orig...

Page 11: ...AL OPTIMA RT10 6K 10K www xmart ups com VER 161205 GA2 ENG 11 VERTICAL MOUNTING UPS can be installed in vertical format by using plastic supports Fig 1 2 These supports are included inside the box 2 M...

Page 12: ...INDEX USER MANUAL OPTIMA RT10 6K 10K www xmart ups com VER 161205 GA2 ENG 12 3 MODULES UPS XBART OPTIONAL ISOTX...

Page 13: ...PTIMA RT 6K and 10K work with 240VDC battery voltage This voltage is provided by battery packs by connecting 20 batteries 12VDC in series There could be some UPS models working with a different DC vol...

Page 14: ...PUT 1 x 120Vac N1 100 Watts SEPARE OUTPUTS 2 x 120Vac N2 50 Watts C U 6KVA with ISOTX Output 110 220V Unique Output Capacity 6000VA 5400W Output Voltage 120Vac AC Breaker 80A Curve D Max Nominal Curre...

Page 15: ...t powered including external batteries UPS XBAT UPS with 220V output generated by UPS inverter This product has 2 basic modules UPS Batteries This UPS can be feed with 220V 240V line L N to generate o...

Page 16: ...module is an optional accessory not included with the UPS It provides 2 galvanic isolated outputs 120V each UPS output is connected to ISOTX input IMPORTANT When ISOTX is connected total power output...

Page 17: ...05 GA2 ENG 17 ISOTX OUTPUTS CONFIGURATION ISOTX outputs can be connected in 3 different configurations according to the needs of the application IMPORTANT When 2 x 120V output configuration is selecte...

Page 18: ...llel connection also allows system can grow in power by adding extra units For working parallel as a parallel system all units must share same AC input and AC output Some control cables must be also c...

Page 19: ...ndable all output neutral lines are connected directly without breakers It is important neutral lines are connected always since neutral is an important electrical reference for all UPS of the paralle...

Page 20: ...ird UPS must be connected following same principle IMPORTANT It is recommendable all output neutral lines are connected directly without breakers It is important neutral lines are connected always sin...

Page 21: ...RTANT It is recommendable all output neutral lines are connected directly without breakers It is important neutral lines are connected always since neutral is an important electrical reference for all...

Page 22: ...d UPS must be connected following same principle IMPORTANT It is recommendable all output neutral lines are connected directly without breakers It is important neutral lines are connected always since...

Page 23: ...GA2 ENG 23 CONTROL CABLES CONNECTION DIAGRAM Parallel system requires all UPS share some important control information by parallel control cables There are 2 kind of control cables SHARED CURRENT PAR...

Page 24: ...t on its terminals If bypass mode is not enable UPS will simply lights its LCD Outputs will keep powered off 2 Bypass mode is adopted as soon as a problem is detected in its internal circuitries 3 Byp...

Page 25: ...SWITCH In case user decides to install a generic external bypass switch without a safety plate status signal the operator will be responsible of setting UPS in static bypass mode before actuating the...

Page 26: ...ies but also feeds rectifier input UPS output is generated by inverter BATTERY MODE A Input indicator at bottom left corner A shows Battery voltage since there is no valid AC input detected B Output i...

Page 27: ...INDEX USER MANUAL OPTIMA RT10 6K 10K www xmart ups com VER 161205 GA2 ENG 27 ERROR FAILURE MODE A When a failure is detected UPS display error code with alert symbol on screen...

Page 28: ...elease before required time UPS will not turn on ENTER When UPS is in configuration mode this key operates as ENTER OFF ESCAPE UPS TURN OFF Press during 2 seconds to turn UPS off SCAPE When UPS is in...

Page 29: ...NFORMATION It displays AC output voltage Output frequency in Hz ALARMS ERRORS This section of the LCD displays active alarms and errors providing codes and descriptive symbols This section also shows...

Page 30: ...5 BYAPSS internal static line active 6 ECO mode active 7 Audible alarm beep muted OUTPUT POWER METER This area displays graphically by a 4 segments bar the power supplied by the UPS 25 Supplied Power...

Page 31: ...Used as key to navigate or changing parameters value ON ENTER Used as ENTER key to confirm modifications MUTE DOWN Used as key to navigate or changing parameters value AVAILABLE FUNCTIONS UNDER EACH...

Page 32: ...e of input frequency If ATO is selected output frequency will be set by input frequency read when UPS started by first time from 46 to 54 Hz will set to 50Hz from 56 to 64 Hz will set to 60Hz IMPORTAN...

Page 33: ...under any condition PAR 03 ENA Enable Bypass allowed in both manual and automatic DIS Disable Automatic Bypass allowed but manual is prohibited Set values with keys 09 MAXIMUM RUNTIME This function s...

Page 34: ...adjusted ADD for increasing SUB for decreasing Set values with keys LCD CODES AND TEXTS TEXT DESCRIPTION BAT Battery Bater a CF Frequency Converter Function Enable Funci n de Convertidor de Frecuencia...

Page 35: ...er input lines ON at electrical board by setting Circuit Breaker to ON 3 Put Battery Bank breaker to ON in case UPS has XBAT connected 4 Put AC INPUT Breaker to ON in UPS rear panel 5 LCD of UPS must...

Page 36: ...ALLEL UPS Check all previous requirements are complied If not do nott try to start ups parallel UPS 1 Check parallel UPS are powered OFF and turned OFF 2 Check all input breakers are in OFF position 3...

Page 37: ...ry backup of remaining UPS could not be enough to keep system running before reconnecting removed unit External breakers could be activated randomly during operation so system could be tripped 3 There...

Page 38: ...ep s HIGH TEMPERATURE 1 beep s CHARGER FAILURE 1 beep s UPS BLOCKED as consequence of detecting 3 overloads in less than 30 minutes OR MBS cover REMOVED 1 beep s ALARMS ALARM CODES Battery Disconnecte...

Page 39: ...VERTER output 14 SHORT CIRCUIT detected at Battery SCR 21 SHORT CIRCUIT detected at inverter output 24 COMMUNICATION CAN error 31 DESBALANCED CURRENT IN PARALLEL SYTEM 36 OVER TEMPERATURE 41 CPU COMMU...

Page 40: ...OLUCION 01 02 03 04 11 12 13 24 6A 6B 6C 60 63 Turn off and power off UPS Disconnect all equipment connected to UPS Restart UPS with no loads connected to its output If UPS starts up without problems...

Page 41: ...ogy VRLA and specifications 12VDC and similar capacity in AH BATTERIES QUANTITY This type of UPS is equipped at factory with 20 batteries 12VDC connected in serial for a total of 240VDC This UPS can b...

Page 42: ...on service partners reserve the right to charge handling fee if returned product is free of failure or it is out of warranty because any of the reasons described in this warranty 6 If product is out o...

Page 43: ...orts Shared Current 3 AC Input Breaker 10 Parallel Control Ports Parallel Control 4 Connector for Ext Bypass status signal 11 FAN UPS 5 DC connector for external batteries 12 FAN ISOTX optional module...

Page 44: ...Pack 1 m dulo de Bater as Additional packs Paquetes adicionales Charging Amps Corriente de Carga Charging Voltage Voltaje Cargador RT10 6KVA 230 RT10 10KVA 230 6 000VA 6 000W 10 000VA 10 000W 220Vac s...

Page 45: ...ed 1 100m over 1 000m La salida se reduce en 1 cada 100m sobre los 1 000msnm Note 4 Bypass mode is prohibited automatically when CF function is activated El modo bypass se anula automaticamente cuando...

Page 46: ...INDEX USER MANUAL OPTIMA RT10 6K 10K www xmart ups com VER 161205 GA2 ENG 46 NOTAS...

Page 47: ......

Page 48: ...USA Headquarters 10540 NW 26th St Doral FL 33172 USA EUROPE Headquarters Ave Can Bordoll 60 Nave 4 Sabadell 08202 Spain Latin America Headquarters Zona Ind San Vicente II C F A11 Maracay Venezuela...

Reviews: