INDEX
USER MANUAL - OPTIMA RT10 6K/10K
www.xmart-ups.com
VER.161205-GA2 (ENG)
26
OPERATION MODES LCD SCREENS (230VAC)
LCD screens for 120V UPS models are similar but showing values related to 120V instead of 230V
OPERATION MODE
DESCRIPTION
LCD
STANDBY
A- When bypass is not allowed UPS output is
powered-off (0V). It happens when UPS
detects a valid input voltage but ON button
has not been pressed.
B- Flow chart indicates AC input is used to
recharge batteries only.
ONLINE
A
–
In online mode, Input voltage indicates a
valid AC input close to (232VAC).
B
–
Output voltage is displayed in upper left
corner (B)
C
–
Flowchart indicates AC input is used to
recharge batteries but also feeds rectifier
input. UPS output is generated by inverter.
BATTERY MODE
A- Input indicator at bottom left corner (A)
shows Battery voltage since there is no valid
AC input detected.
B- Output indicator displays AC output
generated by UPS inverter.
C- AC input symbol must be turned off
representing there is no valid AC input
detected by UPS.
D- Clock symbol lights and backup time is
displayed on the screen.
BYPASS MODE
A- Input and output indicators must show a
similar value since output is been feed by
input through static internal bypass line.
B- Flowchart shows static bypass line is
active. Converters icon is turned off
representing inverter is OFF.
ECO MODE
A- ECO symbol is active on LCD
B- Flowchart indicates output is powered
from input.
FREQUENCY CONVERTER
MODE
A- FC CONVERTER symbol is activated to
indicate FC conversion mode is active.