CONFIGURATION MENU:
This model has configurable functions as listed in below table:
01
OUTPUT VOLTAGE:
- For 220V/230V models: Operator can select between: 208Vac / 220Vac / 230Vac /
240Vac. Factory set to: 230V
- For 120V models: Operator can select between: 110Vac / 115Vac / 120Vac / 127Vac.
Factory set: 120V
02
CF: ENABLE / DISABLE FREQUENCY CONVERTER FUNCTION:
CF can be enable/disable by setting PAR. 03:
CF = Enable
NCF = Disable
If CF is enable PAR 02 must be set to preferred frequency value: 50Hz or 60Hz
This function allows UPS to generate output at selected frequency no matter value of
input frequency
If ATO is selected, output frequency will be set by input frequency read when UPS started
by first time:
from 46 to 54 Hz will set to 50Hz
from 56 to 64 Hz will set to 60Hz
** IMPORTANT:
1)
If CF is active, output power is decreased by 30%. It means max. UPS power will
be 70% of max. rated power. Example: a 10KVA only will be able to supply 7KVA
max.
2)
BYPASS mode is automatically prohibited if CF is activated.
03
BYPASS: INPUT VOLTAGE RANGE
- Valid input VOLTAGE range for bypass mode can be configured by setting high limit
and low limit:
PAR 03: sets high limit (in Vac)
PAR 02: sets low limit (in Vac)
04
BYPASS: INPUT FREQUENCY RANGE
- Valid input FREQUENCY range for bypass mode can be configured by setting high
limit and low limit:
PAR 03: sets high limit (in Hz)
PAR 02: sets low limit (in Hz)
05
ECO ENABLE / DISABLE:
ENA : ENABLE
DIS : DISABLE