ERROR CODES
Error states are produced when UPS detects a critical problem that avoids its normal operation in ONLINE mode. This condition is
described by steady symbol and code on LCD. A continuous beep is also generated by the UPS.
TIPO DE FALLA
CODIGO DE FALLA
SIMBOLO
DC BUS start failure
01
DC BUS High
02
DC BUS Low
03
INVERTER start failure
11
INVERTER High voltage
12
INVERTER Low voltage
13
SHORT CIRCUIT detected at INVERTER output
14
BATTERY voltage too HIGH
27
BATTERY voltage too LOW
28
OVER TEMPERATURE
41
OVERLOAD: Detected at UPS output
43
BATTERY CHARGER Failure
45
AUDIBLE ALARM BEEPS
ERROR:
Continuous Beep
BATTERY MODE:
1 "Beep" / 5s
BYPASS MODE:
1 "Beep" / 10s. This alarm cannot be muted
LOW BATTERY:
1 "Beep" / 2s. This alarm cannot be muted