USER MANUAL - OPTIMA T09 1K/1.5K/2K/3K 

 

 

www.xmart-ups.com 

VER.170502-GA2 (ENG)

 

22 

 

15.

 

SPECIFICATIONS (1/2) 

 

 

 

 

INPUT / ENTRADA

Freq. Range / Rango Frecuencia
Max. Current / Corriente Max. (Model 120Vac)
Max. Current / Corriente Max. (Model 220Vac)

Slew Rate / Segumiento Frecuencia

Output Regulation / Regulación de Salida

Freq. Conversion / Conversión Frec.
EPO /Apagado Emergencia
Progammable Outputs / Salidas Prog.
DC Component / Componente DC

Eco Mode

Inverter Efficiency / Eficiencia Inversor (100%)
Internal Loss / Pérdidas (BTU) @ 100% load

AC Mode / Modo Normal

Battery Mode / Modo Batería

Surge / Contra Picos
Short Circuit / Contra Cortos en la salida
Input Current / Corriente de Entrada
Output Current / Corriente de Salida
Battery Current / Corriente de baterías
Starting Time / Tiempo de Arranque

Type / Tipo
Cap. & Qty
Recharge Time / Recarga
Charging VDC / Voltaje del cargador (Floating)
Shutdown battery Voltage / Voltaje DC Apagado
Charging Amps / Corriente de Carga

EXT. BATT CABINETS (Optional) - BATERIAS EXTERNAS (opcionales)

Standard EXT-BATT pack

41.3A (RMS)

6.9A (RMS)

10.3A (RMS)

13.8A (RMS)

20.6A (RMS)

Range / Rango - 120V

 Model 120V: 80Vac-150Vac @ 100% load     /     Model 120V: 50Vac-150Vac @ 50% load 

Range / Rango - 220V

 Model 220V: 160Vac-300Vac @ 100% load     /     Model 220V: 110Vac-300Vac @ 50% load 

Dynamic Accuracy / Regulación Carga Variable

< +/- 5% Online (variation 0%-100% & 100%-0% R Load)

7s - 10s (@ 100% load)

10.0 Vdc per battery typical (*N4)

12V/9AH x 3 (36VDC)

12V-9Ah x 6 (36VDC)

4 Hours for 90% capacity / 4 Horas para recuperar el 90% de carga

< 100mV

100%~110%: (warning-alarma) /  110%~130%: 5min to OFF /  >130% : 30s to OFF

Battery Mode, Low batt., Overload, UPS Failure / Modo Batería, Baja batería, Sobrecargas, Falla

Circuit Breaker for 3K NEMA models / Disyuntor para modelos de 3K NEMA

Outlets power-off / Apagado de las salidas (400% of nominal current / 5 cycles)

120V MODEL: >800J (L-N, L-G, N-G)   /   220V MODEL: >1250J (L-N, L-G, N-G)

100%~110%: (warning-alarma) /  110%~130%: 5min to bypass /  >130% : 30s to bypass

UPS status, Load level, Battery, Input/Output voltage, Discharge timer, and Fault conditions

Estado del UPS, Consumo, Baterías, Voltaje Entrada/Salida, Autonomía, Diagnostico Fallas

1350W

Y
Y

(100% LOAD: 90%)  -  (75% LOAD: 90%)  -  (50% LOAD: 90%)  -  (25% LOAD: 88%)

Y

Circuit Breaker / Disyuntor

13.8A (RMS)

20.6A (RMS)

27.5A (RMS)

Internal Fuse 80A Fast Action / Fusible Interno 80A Acción Rápida

12V-9Ah x 12 (72VDC) 12V-9Ah x 12 (72VDC)

12V-9Ah x 6 (36VDC)

Sealed Lead Acid VRLA-AGM / Sellada de Libre Mantenimiento VRLA-AGM

Y

PROTECTIONS

Y

3:1 @ 100% load

< 2% @ Linear Load / Carga Lineal 

< 4% @ No Linear Load / Carga no Lineal

0 ms

Pure Sinewave / Sinusoidal Pura

(100% LOAD: 97%)  -  (75% LOAD: 96%)  -  (50% LOAD: 96%)  -  (25% LOAD: 94%)

(100% LOAD: 97%)

(100% LOAD: 91%)  -  (75% LOAD: 90%)  -  (50% LOAD: 90%)  -  (25% LOAD: 88%)

> 0.99 @ 100% load

12V/7AH x 6 (72VDC)

(*N1)   Model 120V: 100/110/115/120/127Vac    -    Model 220V: 200/208/220/230/240Vac

< 5% @ 100% load

1 Hz / s

Y

Capacity / Capacidad (W)

900W

1800W

2700W

Harmonic Distortion / 
Dist. Armónica (THDv)

EFFICIENCY / EFICIENCIA

40 Hz - 70Hz

Y

Y

Y
Y

1K

2K

3K

1000VA

2000VA

3000VA

1.5K

1500VA

Single phase with ground / 1 fase + Tierra

OPTIMA T09

Capacity / Capacidad (VA)

Current Crest Ratio / Factor de Cresta

Battery Mode / Modo Batería

Voltage Output / Voltaje de Salida AC

  +/- 1%

50 Hz +/- 0.1 Hz     -      60Hz +/- 0.1 Hz

OUTPUT / SALIDA

Frequency / Frecuencia (Batt. Mode)

AC to Inverter / Tiempo AC a Inversor

INDICATORS / INDICADORES

Phase / Fases
Power Factor / Factor de Potencia

OVERLOAD/ SOBRECARGA

Waveform / Forma de Onda

AC Mode / Modo AC

Input THDi / THDi de Entrada

BATTERIES / BATERIAS

LCD

ALARM / ALARMAS

Alarm Beep / Alarma Sonora:

1.5 A (Max.)

12V/9AH x 6 (72VDC)

12V/7AH x 3 (36VDC)

Y

Y

276

414

491

737

41.0VDC

41.0VDC

82.1VDC

82.1VDC

Summary of Contents for OPTIMA T09 1K

Page 1: ...is manual is property of XMART This manual Information cannot be copied or distributed totally or partially without written approval of XMART XMART can introduce modifications in their products or man...

Page 2: ...CTIONS 2 SAFETY QUALITY AND PERFORMANCE STANDARDS 3 PRODUCT DESCRIPTION 4 INSTALLATION 5 OPERATION MODES 6 OPERATION INTERFACE KEYBOARD LCD 7 UPS CONFIGURATION 8 ERROR ALARMS CODES 9 TROUBLESHOOTING 1...

Page 3: ...acelets etc because they could contact conductive parts and components inside the UPS and this might cause discharges and or short circuits Make sure using tools properly isolated to avoid electrical...

Page 4: ...additional measures only for 220 230 240VAC systems NOTE FOR 110 120 VAC SYSTEMS This equipment has been tested and found to comply with the limits for a Class A digital device pursuant to part 15 of...

Page 5: ...printers Xerox copiers or scanners requires high peak power that can overload this UPS User must size UPS to maximum power required by load IMPORTANT Do not connect big loads based on AC motor or high...

Page 6: ...d on the rear panel of the UPS to confirm it marches with DC voltage provided by XBAT DC Voltage for standard T09 models T09 1K 36VDC T09 1 5K 36VDC T09 2K 72VDC T09 3K 72VDC 1 Place UPS module close...

Page 7: ...d off 2 Bypass mode is adopted as soon as a problem is detected in its internal circuitries 3 Bypass mode is also activated in case an external overload is detected in UPS output It happens when equip...

Page 8: ...ng there is no valid AC input detected by UPS D Clock symbol lights and backup time is displayed on the screen BYPASS MODE A Input and output indicators must show a similar value since output is been...

Page 9: ...UPS TURN OFF Press during 2 seconds to turn UPS off ENTER When UPS is in configuration mode this key operates as ENTER SELECT CHECK VALUES UPS can show in alternative cycle all available values by pus...

Page 10: ...T INFORMATION It displays AC output voltage Output frequency in Hz ALARMS ERRORS This section of the LCD displays active alarms and errors providing codes and descriptive symbols This section also sho...

Page 11: ...ed 5 BYAPSS internal static line active 6 ECO mode active 7 Audible alarm beep muted OUTPUT POWER METER This area displays graphically by a 4 segments bar the power supplied by the UPS 25 Supplied Pow...

Page 12: ...n configuration mode LCD displays ID of the menu and values of 2 adjustable parameters 1 MENU ID 2 Function name 3 Configurable value KEYBOARD IN CONFIGURATION MODE ON MUTE Used as key to navigate or...

Page 13: ...0Hz 04 ECO ENABLE DISABLE ENA ENABLE DIS DISABLE Factory set DIS Check more details at operation modes section 05 ECO INPUT VOLTAGE RANGE Vac Function 02 High Limit Function 03 Low Limit Set values wi...

Page 14: ...IN AH This function must be adjusted only if external batteries are connected to the UPS Adjusted value must describe total AH internal external connected to UPS For example if UPS has internal bank o...

Page 15: ...Frequency Converter Function Funci n de Convertidor de Frecuencia CHA Charger current Corriente del Cargador de Bater as CH Charger Cargador de Bater as ESC Escape Salir ON ON Encendido ENA Enable Hab...

Page 16: ...ALARM ALARM SYMBOLS AUDIBLE BEEP OVERLOAD detected at UPS output 1 beep s LOW BATTERY 1 beep 2s BATTERY DISCONNECTED OR FAULTY 1 beep 2s BATTERY REPLACEMENT REQUIRED 1 beep 2s BATTERY DISCONNECTED 1 b...

Page 17: ...TIPO DE FALLA CODIGO DE FALLA SIMBOLO DC BUS start failure 01 DC BUS High 02 DC BUS Low 03 INVERTER start failure 11 INVERTER High voltage 12 INVERTER Low voltage 13 SHORT CIRCUIT detected at INVERTE...

Page 18: ...ervice EEPROM Failure Turn off and power off UPS Restart UPS If not solved call technical service ERROR CODES PROBABLE CAUSE SOLUCION 01 02 03 Turn off and power off UPS Disconnect all equipment conne...

Page 19: ...atically battery life IMPORTANT RECHARGING PLAN FOR LONG STORAGE If UPS will be stored for long time it is mandatory to recharge UPS periodically If UPS is not recharged according to this plan batteri...

Page 20: ...ution service partners reserve the right to charge handling fee if returned product is free of failure or it is out of warranty because any of the reasons described in this warranty 6 If product is ou...

Page 21: ...170502 GA2 ENG 21 14 FRONT REAR PANEL 1 Standard UPS Outlets 6 Emergency Power Off connector 2 Programmable Outlets 7 USB RS232 3 AC Input 8 Intelligent port 4 Input AC Breaker 9 DC connector for ext...

Page 22: ...models Disyuntor para modelos de 3K NEMA Outlets power off Apagado de las salidas 400 of nominal current 5 cycles 120V MODEL 800J L N L G N G 220V MODEL 1250J L N L G N G 100 110 warning alarma 110 13...

Page 23: ...p time for programable outlets can be configurable in minutes Las salidas programables pueden configurarse en minutos N4 Shutdown voltage depends of load runtime Voltaje de corte de bater as depende d...

Page 24: ...NOTAS...

Page 25: ......

Page 26: ......

Page 27: ......

Page 28: ...NW 26th St Doral FL 33172 USA sales xmart ups com EUROPE Ave Can Bordoll 60 Nave 4 Sabadell 08202 Spain sales xmart ups com Latin America Zona Ind San Vicente II C F A11 Maracay Venezuela sales xmart...

Reviews: