2.
SAFETY, QUALITY AND PERFORMANCE STANDARDS
SAFETY - LOW VOLTAGE DIRECTIVE (2006/95/EC)
UPS Part 1-1: General & Safety UPS in accessible areas
IEC/EN 62040-1
ELECTROMAGNETIC COMPATIBILITY - EMC DIRECTIVE (2004/108/EC)
UPS, Part 2, Electromagnetic Compatibility:
IEC/EN 62040-2
Low Freq. Conducted Disturbances & Signals:
IEC/EN 61000-2-2
Electrostatic discharge immunity Test:
IEC/EN 61000-4-2 (Level 3)
Radiated radio Frequency immunity:
IEC/EN 61000-4-3 (Level 3)
Electrical Fast Transient / burst immunity:
IEC/EN 61000-4-4 (Level 4)
Surge immunity:
IEC/EN 61000-4-5 (Level 4)
Conducted Immunity:
IEC/EN 61000-4-6
Power frequency magnetic field immunity:
IEC/EN 61000-4-8
Voltage Dips, Short Interruptions & Voltage Variations Immunity:
IEC/EN 61000-4-11
PERFORMANCE: UPS Part 3: Methods of operation, specs and test requirement
IEC/EN 62040-3
IT Equipment. SAFETY. Part 1: General Requirements
IEC/EN 60950-1
BATTERY SAFETY
EN 50272
UL1778 (for UL models only)
UL1778 compliant (by cTUV-US)
IP PROTECTION
IP20 (static)
QUALITY MANAGEMENT:
Manufactured under:
ISO 9001 : 2008
ENVIRONMENTAL MANAGEMENT:
Manufactured under:
ISO 14001 : 2015
TRANSPORTATION:
IEC/EN 60068-2-32 (Drop Test)
IEC/EN 60068-2-64 (Vibration Test)
IEC/EN 60068-2-27 (Shock Test)
WARNING: Modifications made on the product or the use of this product as a part of a more complex system not expressly approved by the party
responsible for compliance could void the user’s authority to operate the equipment. It also could affect its performance and
the compliance of
regulations. XMART is not responsible of modifications made after manufacturing.
WARNING: This is a category C2 UPS product. In a residential environment, this product may cause radio interference, in which case the user
may be required to take additional measures (only for 220/230/240VAC systems).
NOTE FOR 110/120 VAC SYSTEMS: This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to
part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when equipment is operated in
a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance
with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely
to cause harmful interference in which case the user will be required to correct the interference at his own expense.
3.
PRODUCT DESCRIPTION
This is an Uninterruptible Power Supply (UPS) ONLINE DOUBLE CONVERSION with IGBT technology at rectifier and inverter stages with
PWM modulation. It generates a pure SINEWAVE output free of noise and imperfections for powering and protecting your valuable
system. This UPS is the right choice to protect hardware and data in critical workstations and server applications.
This product has been designed to operate under hostile electrical conditions but offering a reliable performance with outstanding
features and characteristics. Optima T09 is equipped with a powerful anti-surge system based on MOV technology. This model has
filtering circuits for EMI interferences. It is 100% compatible to operate connected to low quality AC sources like power generators. Soft-
start function allows connection to AC input source is done only when AC input values are confirmed inside operational ranges.
Our monitoring software allows configuring and controlling this UPS by any of available communications ports: USB/RS232 or LAN
Ethernet optional card (under SNMP protocol).
OPTIMA T09 series has 4 different models for supporting all kind of applications from 1KVA to 3KVA:
T09 1K: 1.000VA/900W
T09 1.5K: 1.500VA/1.350W
T09 2K: 2.000VA/1.800W
T09 3K: 3.000VA/2.700W