background image

These models are permanently

connected to the supply and

operation is controlled by a remote

switch.

They should be directly wired to the

supply through an approved 10A wall

mounted surface switch with

at least 3mm clearance between

contacts.

If working above ground level,

appropriate safety precautions must

be observed.

WARNING: EYE PROTECTION MUST

BE WORN DURING ALL DRILLING

AND CHISELLING OPERATIONS.

1. Check there are no buried pipes 

or cables in the wall or obstructions

on the outside (eg: electricity,

gas, water).

2. Ensure that the centre of the hole 

is located at least 145mm from the 

edges of the wall.

3. Mark on the centre of the duct hole.

4. Use this centre to draw a circle to 

suit the wall duct (203mm diameter 

for a WK6/300 or WK6/450).

5a.Use as directed by the core drill 

manufacturer.

5b. Drill a centre hole right through the 

wall.

5.  Cut the hole. Do not cut right 

through the wall (the recommended

method is to drill a series of holes, 

close together, around the edge of 

the cutting line and remove the brick 

between the holes with a chisel).

7.  Go outside and cut a hole in the 

outer wall, repeating the process 

described above.

8.  Fit the ducting. Ensuring that the 

duct slopes down away from the fan 

to allow drainage of any incoming

rain water to the outside.

9.  Make good the hole. Allow for mortar

to set before continuing with the 

installation.

Obtain a ready cut pane with a correctly

located hole 184mm diameter. (See Fig.A).

1.  For window mounting, use the two 

short ladder strips supplied with the 

fan. 

For Wall mounting, use the longer 

strips supplied with the wall kit 

WK6/300 or WK6/450.

2.  Secure the two ladder strips to the 

outer grille by positioning them over 

the hook moulding and snapping

into position.

3. Ensure after fitting the hook moulding

that the gasket is in the correct 

position. (See Fig.B).

4. Insert the two screw covers in the 

two fixing holes in the outer grille.

If working above ground floor level, 

appropriate safety precautions must 

be observed.

Remove the Back Draught Shutter/Grille

Assembly, by pressing the release

catches located on the sides of the unit

with a 6mm screwdriver or coin, whilst

pulling the grille forward.

1. Hold up the outer grille to the 

outside of the wall or window so that 

the hole in the outer grille is aligned

with the hole in the wall or window.

2. If wiring from the rear, remove the 

fans terminal cover and rear entry 

knockout. Feed the cable through

the top cable entry.

2b. If wiring from above, remove fans 

terminal cover and feed the cable 

through the top cable entry.

2c.

For GX6 (IP25) only

, wiring from 

above, remove fan’s terminal cover. 

Pierce the cable entry grommet with 

a No. 1 screwdriver and feed the 

cable through the top cable entry via 

the grommet. DO NOT REMOVE 

THE GROMMET.

3. Hold the fan assembly to the inside 

of the wall or window and guide the 

ladder strips from the outer

grille through the slots in the fan 

assembly.

4. Insert the slotted screws into the 

pockets around the ladder strip slots.

5.  Tighten the screws carefully to make 

a good seal. Do not over tighten the 

screws.

6.  Trim the ladder strips back to the 

required length, if necessary remove 

any sharp edges.

1.  Hold the outer grille up to the 

outside of the wall so that the hole in 

the outer grille is aligned with the 

hole in the wall.

2.  Mark the positions of the fixing holes 

in the top right and bottom left 

corners.

3.  Drill the holes and insert anchor 

fixings to suit the wall.

4.  Screw the outer grille securely in 

place and fit screw caps in place. 

Do

not over tighten screws.

5.  Insert the two screw covers in the 

two fixing holes in the outer grille.

6a. If wiring from the rear, remove the 

fans terminal cover, and rear entry 

knockout. Feed the cable through the

knockout.

6b. If wiring from above, remove the fans

terminal cover and feed the cable 

through the top cable entry.

6c.

For GX6 (IP25) only,

wiring from 

above, remove fan’s terminal cover. 

Pierce the cable entry grommet with 

a no. 1 screwdriver and feed the 

cable through the top cable entry via 

the grommet. 

DO NOT REMOVE 

THE GROMMET.

7.  Hold the fan assembly to the inside 

of the wall so that the spigot is 

inserted into the wall duct.

8.  Mark the position of the two fixing 

holes in the top left and bottom right 

corners.

9.  Remove the fan assembly, drill the 

holes and insert anchor fixings 

appropriate to the type of wall.

10. Reposition the cable and fan 

assembly as before, and screw 

securely in place. 

Do not over 

tighten screws.

Note: For particularly difficult

installations, it is possible to secure the

fan with a combination of screw and

ladder strip fixings.

1. Wire the switch cable into the 

terminal connections shown:

Fig.E1 for GX6 / GXC6 / GXC6T / 

GXS6 / GX6 (IP25).

Fig.E2 for GX6T / GX6HT.

Fig.E3 for GXHT2.

2.  If the fan is wired from above, 

ensure the outer sheath of cable is 

retained in the labyrinth (see Fig.C).

3.  Refit and secure terminal cover.

4.  Refit the back draught shutter/grille 

assembly by sliding the grille back 

over the release catches, the 

catches will locate and secure the 

grille.

5. 

Switch off the mains electricity 

supply and remove fuses.

6.  Connect the cable from the isolation 

switch to the electrical supply wiring.

7.  Replace the fuses and switch on the 

mains electrical supply.

For fixed wiring circuits the protective

fuse for the appliances must not

exceed 5A.

Note: If using an external boost switch

for the GX6HT2 (see Fig.E3), cut off the

pull cord after ensuring that it is

in the “off” position. This switch must be

marked with suitable markings to

indicate speed control.

These fans are single speed, except 

the GX6HT2 which is two speed, and 

all are non reversible (extract only).

The shutters have a time delay of up 

to 1 minute on opening and up to 3 

minutes on closing. Activated by

operation of the switch, the delay 

ensures quiet operation (except 

GXC6 and GXS6 models).

For Australia Only: WARNING – Children should

not play with the appliance. Young children and

the infirm should be supervised.

The fan is operated by a remote 
switch.

The fan is operated by an integral pull

cord.

To switch on, pull down the cord and 

then release it.

Repeat to switch off.

The fan is operated by an integral pull

cord.

To switch on, pull down the cord and 

then release it.

Repeat to switch off.

The integral timer provides an 

adjustable overrun period after the 

fan has been switched off.

Preparing the hole

Preparing the Fan for

installation

If fixing with ladder strips

If installing in a window

For Australia only

If installing in a wall

If core drill equipment is available

If core drill equipment is not

available

Mounting the fan in the hole

Fig. C

If using screw fixings

Wire the electrical connection

Operating the Fan

GX6

GXC6

GXC6T

Summary of Contents for GX6

Page 1: ...and maintenance instructions Retain for future reference GB F D NL I a NO GR Internal External Wall Window Fan Range Do read all the instruction leaflet before commencing installation Do install each...

Page 2: ...A B C D GLASS WINDOW 6 see F 13...

Page 3: ...E1 E2 E3...

Page 4: ...G1...

Page 5: ...G3 G2...

Page 6: ...wJ A B hJ c E g Hy 6H w9 enJ 550 9 kd8d i foK 0 C Ed i K 3d d hBz h Iz f Dz x K yE 3d o E t i g eG F hBz E k 3d E E BxiE f oiE 0 C Ed x h e F 7I fo B x E E fr h Iz F 0 dD 1 E xC F I haBxiE 0d h x K i...

Page 7: ...F xD diE L I F f D Ed K yE u E i K d 8 E1 d 6du 5 eC F xui 4 E Ld F E 3d yH he 4d I 4d 3d kdCd I h I h kdCd KxE KyE d E I kd d I 5 x hBz FI KxE E KyE iF 4 I F u 5 h 4 3d xui 4 3d d e E x F xD di E d...

Page 8: ...LEAVE THIS LEAFLET WITH THE FAN FOR THE BENEFIT OF THE USER Installing the fan Description GX6 GXC6 GXC6T GX6T GX6HT GX6HT2 GXS6 GX6 IP25 What the installer will need If window mounting the fan you wi...

Page 9: ...n the outer grille is aligned with the hole in the wall 2 Mark the positions of the fixing holes in the top right and bottom left corners 3 Drill the holes and insert anchor fixings to suit the wall 4...

Page 10: ...airbrick or similar device 1 Remove the back draught shutter grille assembly see Mounting the fan in the hole section 2 HOLD THE SHUTTER VANES FULLY OPEN 3 Push down firmly on the trickle vent catch u...

Page 11: ...c voyant incorpor Pour un d clenchement appareil d appoint ext rieur il faut pr voir deux commutateurs Tournevis grosse lame de 6 mm tournevis d lectricien lame de 3 mm tournevis Pozidriv n 1 et 2 Une...

Page 12: ...2 Poser le c ble entre le bouton sectionneur et l emplacement du ventilateur en passant par l interrupteur de marche arr t Cf Fig E1 SW1 Cf Fig E2 et l interrupteur de relais ext rieur SW1 Cf Fig E3...

Page 13: ...elister Installering i vindu Kun for Australia Installering i vegg Hvis du har tilgang til kjerneborutstyr Hvis du ikke har tilgang til kjerneborutstyr Montere viften i hullet Fig C Ved feste med skru...

Page 14: ...mottrekksklaffer for umiddelbar pning og lukking Innstilling av dryppventilering For bruk med fjerntliggende bryter Utsug ved enkel hastighe Innstilling av dryppventilering IP25 inngangsvern En skill...

Page 15: ...rsi Nei modelli GXC6 e GXS6 l operazione di pulizia pu essere iniziata non appena la girante ha smesso di ruotare 2 Togliere il gruppo serranda di controtiraggio grata premendo i fermi di sgancio ubic...

Page 16: ...t in einen Rauchkanal abgef hrt werden der f r den Abzug von Abgasen nichtelektrisch betriebener Ger te vorgesehen ist F r die Ausleitung von Abluft und Zuluftstr mungsgeschwindigkeite n m ssen die Vo...

Page 17: ...trattore per l installazione In caso di fissaggio con i listelli a scala In caso di installazione in finestra Solo per l Australia In caso di installazione a parete Se si dispone di un allargatore di...

Page 18: ...entellinare Per funzionamento con interruttore a distanza Temporizzatore igrostato incorporato Estrazione ad una velocit Impostazione di ventilazione centellinare Per funzionamento con interruttore a...

Page 19: ...Siehe Abb F Punkt 6 4 Trek de klem van de druppelventilatie naar u toe tot hij op z n plaats klikt 5 Breng de jalouzie afsluiter roosterassemblage weer aan zie de sectie Bevestiging van de ventilator...

Page 20: ...te of badkamer moet het zo zijn geplaatst dat het niet door personen die een bad of douche nemen kan worden aangeraakt 1 Controleer of er geen verborgen leidingen bijvoorbeeld elektriciteit gas water...

Reviews: