 replacement at the same time as the other MVHR Filters.  

 

Please contact the UK sales office for further details, contact details can  
be found on the back of this booklet. 

 

Please note: 
If the external air is drawn in via a geothermal Heat Exchanger, a class  
G4 Filter should be installed in the intake tower. 
 

 

12.  Cleaning the Recuperator 

 
The Recuperator should be cleaned by a specialist technician 
as and when required depending on the level of contamination, 
but at least every 2 years. Contact details for servicing by  
Xpelair approved technicians can be found on the back of this  
booklet. The cleaning procedure is as follows:  

 

1.  Disconnect the MVHR from the mains supply 

 

2.  Remove the  top cover 

 

3.  Remove the Retaining Bracket located in front of the                                                                                                          Heat Exchanger by removing the screw 

 

4.  Carefully pull the Recuperator outwards using the black                                                                                                                                                              plastic 

strap around the Heat Exchanger, keeping it                                                                                                                    horizontal to avoid damaging the EPP housing 

 

5.  Thoroughly rinse the Recuperator with lukewarm water and allow all the water to drain off 

 

6.  Residual moisture will evaporate when the MVHR is operated 

 

7.  Carefully insert the cleaned Recuperator, keeping it parallel to avoid damaging the EPP housing 

 

8.  Replace the Recuperator Retaining Bracket and retaining screw 

 

9.  Switch the mains supply back on 

 

10.  The MVHR is ready to recommence operation 

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

13.  Troubleshooting 

 
Important:

  

 

 
Servicing of the MVHR may only be carried out by a qualified service technician.  
Contact details for servicing by Xpelair approved technicians can be found on the back of this booklet. 
 

 
13a. Fault locating table 

 

SYMPTOM 

CHECK 

POSSIBLE CAUSE 

Fan does not work 

                                                      
The mains supply is on 
 

 

Mains supply interrupted 

Fuse has blown:  

Mains supply fuse or supply cord plug fuse 

Supply air Fan defective  

Exhaust air Fan defective 

Fan blade catching on inner EPP housing  

Contact fault on Fan control or power leads 

 

Control PCB defective 

 

Supply air and/or exhaust 
air flow rate is too low 

 
Filters 
Room air valves 
Outside grilles 
 

Filter service period has expired  

No water coming through 
Condensate Drain Tube 

 
Correct connection 
Connection to dwelling Building 
Waste System and not directly 
outside 
 

No water in siphon 

Condensate water drain blocked 

Noise coming from the 
MVHR unit 

Fans are noisy 

 

Increased air resistance due to contami-
nated Filters and/or Heat Exchanger 

Obstruction in the duct system  

 

Summary of Contents for Xcell Stratum S120Q

Page 1: ...Installation and user manual Xcell Stratum S120Q Mechanical Ventilation Unit with Heat Recovery Please ensure these instructions are kept safe and accessible at all times...

Page 2: ...7 5 6 Installation dimensions 8 6 Technical Data 8 6 1 Technical data 8 6 2 Accessories 8 6 3 Replacement filters 9 7 Electrical Wiring Diagram 9 7a Electric wiring 2 way switch 9 7b Electric wiring...

Page 3: ...s they have been given supervision or instruction concerning use of the appliance by a person responsible for their safety Ensure that all relevant safety precautions correct eye protection and protec...

Page 4: ...heated external air is distributed into the house and the cooled exhaust air is ducted out of the building 4 3 MVHR installation planning MVHR system designs must comply with the current standards go...

Page 5: ...rong odours which could then permeate into the MVHR and contaminate the fresh air supplied from the MVHR unit The following must also be met Access is required for maintenance work e g changing the fi...

Page 6: ...ters a frost protect pre heater is recommended All ducting fitted to the spigots on the MVHR should be secured via a suitable sealed duct connector to prevent air leakage e g Xpelair CPC125 91485AA Du...

Page 7: ...d annually and cleaned if necessary A condensate drain tube 20mm and 1 0m long is supplied The water trap must be purchased separately from a local plumbing stockist 5 5 Typical installation example 1...

Page 8: ...C 20 to 40 Dimensions without ducting W x H x D mm 550 x 240 x 510 Weight of MVHR Kg 10 Duct connections mm 125 4xDN125 Condensate drain tube connections mm 20 Filter class F5 Efficiency of Recuperat...

Page 9: ...6 3 Replacement filters Description Part Number Replacement filters set of 2 40552AA 7 Electrical Wiring 7a Electrical Wiring to a two way switch 9...

Page 10: ...ng a common and high or low 7 1 Set up procedure Move jumper to Test 1 position Balance system to desired normal extract rate using pot speed 1 Move jumper to Test 2 position Balance system to desired...

Page 11: ...d and cleaned at least twice a year and replaced at least on an annual basis The original external exhaust F5 quilted filters are enclosed in a frame Contact details for purchasing new filters or serv...

Page 12: ...MVHR is operated 7 Carefully insert the cleaned Recuperator keeping it parallel to avoid damaging the EPP housing 8 Replace the Recuperator Retaining Bracket and retaining screw 9 Switch the mains su...

Page 13: ...13 Room air regulator valves not open wide enough Note This table may be subject to technical amendments...

Page 14: ...four retaining screws to remove the plastic Motor Mount from the faulty fan noting the orientation of the faulty fan and it s leads in relation to the slots in the plastic motor mount f Assemble the...

Page 15: ...ge made EXCLUSIONS This guarantee does not apply to the repair or replacement of filters accessories isolating switches electrical cable fuses and or circuit breakers or annual servicing This guarente...

Reviews: