background image

3.1. Plumbing Connections 

 

Only DZ rated brass compression type fittings may be connected directly to the collector (soft /silver solder and or brazing may not be used 
on the collector itself), the collector connections (“in and out” Supply/ return) should always be cross directional (i.e. water supplied to 
collector enters the collector through the bottom right connection and leaves the collector through the top left connection), the two 
connection points not used to transport fluid to and from collector should be stop ended, if more than two collectors are to be connected in 
parallel, suitable expansion loops must be added between the collectors, no more than 6 x 2sqm Collectors may be connected in this 
configuration, however multiple banks of 6 collectors may be connected in series. 

 

When tightening the compression fittings two shifting spanners or a shifting spanner and water pump pliers must be used to avoid 
damaging the collector pipe work. 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 
 

3.2. Breather holes and vent caps 

 

Located at the top and bottom of the collector are four breather holes (two either side), (8mm brass rivnuts), these “breather holes” allow 
air flow through the collector and limit condensation from occurring within the collector. These holes must never be covered or used for the 
purpose of mounting, supplied with every collector (clear plastic bag in box) are two Vent caps, these caps are to be screwed into the two 
breather holes located at the top of the collector, these vent caps prohibit the ingress of water and debris whilst allowing moist air to escape. 

 

Summary of Contents for Flat Plate Collector

Page 1: ...In association with Solar Lifestyle CC Mounting Installation Instructions Flat Plate Collector ...

Page 2: ...oduction 2 Mounts and attachments 2 1Mounting components 2 2Tiled roof installation 2 3Sheet roof installation 2 4Flat roof installation 3 Collector Installation 3 1Plumbing connections 3 2Breather holes and vent caps ...

Page 3: ...plate collectors it must be read in conjunction with the system specific installation manual it does not seek to defy logic and or the experience of suitably trained installers use discretion 2 Mounts and attachments Before mounting the collector note that the collector has a right Side up sticker located on the top right side on the top left side of the collector below the 22mm pipe protrusion th...

Page 4: ...the collector size once a suitable distance has been measured replace the tiles carefully so that the opposite hooked part of the S bracket is all that is visible this will provide a slot for the bottom of the collector to be placed in Once the bottom of the collector is secure use the U brackets 2 of to secure the top locate the timber trusses on the side or on top of collector insert the U brack...

Page 5: ...ll not always be possible to align the u brackets to the timber structure using the top edge of the collector in this instance side mounts would be acceptable provided the mounts are placed at least three quarters of the length of the collector 1333mm from bottom of collector See above pictures for variation 2 4 Flat roof installation See instruction manual on assembly of Flat roof frame Secure th...

Page 6: ... Collectors may be connected in this configuration however multiple banks of 6 collectors may be connected in series When tightening the compression fittings two shifting spanners or a shifting spanner and water pump pliers must be used to avoid damaging the collector pipe work 3 2 Breather holes and vent caps Located at the top and bottom of the collector are four breather holes two either side 8...

Reviews: