Studer Innotec SA
Xtender
User manual
V4.6.0
51
Access
level
Param.
N°
Denomination / description
Fact. value
2
Mod.
value
Expert
1405 Time period for critical batteries undervoltages
counting
10 sec
Inst.
1415 ON of the Xtenders
-
Inst.
1432 Absolute max limit for input voltage
270 Vac
Expert
1433 Adaptation range of the input current according to
the input voltage
10 Vac
Expert
1436 Overrun AC source current limit without opening the
transfer relay (Input limit)
Yes
Inst.
1437 Minigrid compatible
No
Expert
1438 Solsafe presence Energy source at AC-Out side
No
Expert
1439 Contact activated with the SOC 1 of battery (AUX 1)
No
Expert
1440 Contact activated below SOC 1 (AUX 1)
50 % SOC
Expert
1441 Contact deactivated over SOC (AUX 1)
90 % SOC
Expert
1442 Contact activated with the SOC 1 of battery (AUX 2)
No
Expert
1443 Contact activated below SOC 1 (AUX 2)
50 % SOC
Expert
1444 Contact deactivated over SOC (AUX 2)
90 % SOC
Inst.
1446 Contact activated with the temperature of battery
(AUX 1)
No
Inst.
1447 Contact activated over (AUX 1)
3 °C
Inst.
1448 Contact deactivated below (AUX 1)
5 °C
Inst.
1457 Contact activated with the temperature of battery
(AUX 2)
No
Inst.
1458 Contact activated over (AUX 2)
3 °C
Inst.
1459 Contact deactivated below (AUX 2)
5 °C
Expert
1461 Multi inverters allowed
Yes
Expert
1462 Multi inverters independents. Need reset {1468}
No
Expert
1467 Force phase of floating
-
Expert
1468 Reset of all the inverters
-
Expert
1485 Prohibited ground relay
Yes
Expert
1486 Continuous neutral
No
Expert
1491 Generator control active
No
Expert
1492 Starter pulse duration (with AUX2)
3 sec
Expert
1493 Number of starting attempts
5
Expert
1494 Time before a starter pulse
3 sec
Expert
1497 Combination of the events for the auxiliary contact
(AUX 1)
Any (Function OR)
Expert
1498 Combination of the events for the auxiliary contact
(AUX 2)
Any (Function OR)
Expert
1505 Delta frequency allowed above the standard input
frequency
35 Hz
Expert
1506 Delta frequency allowed under the standard input
frequency
15 Hz
Expert
1507 Duration with frequency error before opening the
transfer
5 sec
Expert
1510 Tolerance on detection of AC-input loss (tolerant UPS
mode)
100
Expert
1512 Security, maximum time of contact (AUX 1)
No
Expert
1513 Security, maximum time of contact (AUX 2)
No
Expert
1514 Maximum time of operation of contact (AUX 1)
600 min
Expert
1515 Maximum time of operation of contact (AUX 2)
600 min
Expert
1516 Deactivate if battery in floating phase (AUX 1)
Yes
Expert
1517 Deactivate if battery in floating phase (AUX 2)
No
Expert
1518 Xtender ON (AUX 1)
No
Expert
1519 Xtender ON (AUX 2)
No
Expert
1520 No overtemperature (AUX 1)
No
Expert
1521 No overtemperature (AUX 2)
No