background image

Xtreme Power Conversion Corporation

XVT User’s Manual

Page 12

Uninterruptible Power Supply

Specifications

MODEL NUMBER

XVT-600

XVT-800

XVT-1200

XVT-1500

INPUT

Capacity

600VA (360W)

800VA (480W)

120VA (720W)

1500VA (900W)

Voltage

120VAC

Frequency

60Hz ± 5Hz

OUTPUT

Voltage

120VAC

Waveform

Sine wave (normal), simulated sine wave (battery mode)

Frequency

AC mode follows utility battery mode 60Hz ± 0.5Hz

Transfer time

4 ms (typical)

Surge protection

320 joules

Input protection

Compliance with IEEE 587

Short circuit

Breaker

BATTERY

Battery type

Sealed, maintenance-free lead acid

Battery quantity and size

(1) 12V 7AH

(1) 12V 9AH

(2) 12V 7AH

(2) 12V 9AH

Recharge

Less than 10 hours 100% capacity (2 hours typical)

Backup time

3 min (100% load) ≥ 8 min (50% load)

Charge current

1.5A (max)

PHYSICAL

UPS dimensions (W x D x H)

3.7 x 14.6 x 6.2 in

4.9 x 16.9 x 8.7 in

Shipping dimensions

6.1 x 16.2 x 10.2 in

7.5 x 18.9 x 12.8 in

UPS weight

15.3 lbs

16.8 lbs

27.6 lbs

31.3 lbs

Shipping weight

17.6 lbs

19.2 lbs

29.8 lbs

32.4 lbs

Line cord

6 ft, NEMA 5–15P

Receptacles

(6) NEMA 5–15R (3 surge protected; 3 battery back up)

ENVIRONMENT

Operating temperature

32–104°F (0–40°C)

Humidity

0–90%

Audible noise

< 45 dBA

Altitude

11,500 ft above sea level

INDICATORS &

AC mode

Green LED, orange LED on, red LED off, no beep

ALARMS

Charging battery

Orange LED on until 80% charge

Battery mode

Green and orange LED off, red LED flash, buzzer slowly beeps

Battery low

Green and orange LED off, red LED, buzzer beeps quickly

APPROVALS

UL, cUL, FCC

WARRANTY

2 years electronics, 2 years battery (USA and Canada)

COMMUNICATIONS INTERFACE

USB

INCLUDED IN BOX

PowerManager CD, USB cable, user manual

Summary of Contents for 1500VA

Page 1: ...XVT Line Interactive Tower UPS 600VA 800VA 1200VA 1500VA Models User Installation Manual www xpcc com 2015 Xtreme Power Conversion Corporation All rights reserved Rev 1 26 15 ...

Page 2: ...ining The Power Requirements Of Your Equipment 6 HardwareInstallationGuide 6 Quickstart Software Installation Guide For Windows 7 Functions 8 Replacing The Battery 9 Definitions For Led Indicators 9 Alarms 10 Troubleshooting 11 Specifications 12 ShippingList 13 Obtaining Service 14 Xtreme Power Conversion Limited Warranty 15 Xtreme Power Conversion Load Protection Policy 16 ...

Page 3: ...icular installation If this equipment does cause harmful interference to radio or television reception which can be determined by turning the equipment off and on the user is encouraged to try to correct the interference by one or more of the following measures 1 Reorient or relocate the receiving antenna 2 Increase the separation between the equipment and receiver 3 Connect the equipment into an ...

Page 4: ...t care NOTICE Not for use in a computer room as defined in the Standard for Protection of Electronics Computer Data Processing Equipment NOTICE An acceptable outlet based upon UPS Specifications shall be installed near the equipment and shall be easily accessible Product Description UPS Functionality The XVT UPS products use Line Interactive Automatic Voltage Regulation AVR UPS technology Under no...

Page 5: ...nt during a power failure Power Switch Can be used as a master on off switch for equipment connected to the battery powered outlets Power On Indicator This LED is illuminated when the utility condition is normal and the UPS outlets are providing power free of surges and spikes Circuit Breaker The circuit breaker that provides overload and fault protection USB Port protocol that provides communicat...

Page 6: ...he battery with the power switch in either the on or off position 2 With the UPS off and unplugged connect your computer monitor and or any other externally powered equipment into the battery power supplied outlets DO NOT plug a laser printer copier space heater vacuum or other large electrical device into the UPS The power demands of these devices will overload and possibly damage the UPS 3 Plug ...

Page 7: ...xe UPSilon files will be copied into the directory you appoint 5 Follow the software setup prompts 6 When UPSilon has been launched the operating system will select the local language for displaying UPSi lon 7 Select UPSilon 2000 for Windows for parameter settings 8 Click Select UPS to monitor local or remote UPS 9 Select Settings to set Communication Type and Select Comm Port If Communication wit...

Page 8: ...ssible with information including input voltage output voltage line frequency bat tery capacity load temperature etc Section 2 is the UPS Status Area shows whether the UPS is connected to the computer if AC power is in normal range status of the UPS and relevant information regarding the UPS Section 3 is the Function Selection Area allows configuration of the parameter values After selecting to mo...

Page 9: ...ctrical shock The short circuit current capability of the battery is sufficient to burn wire or tools very rapidly producing molten metal Observe these precautions when replacing the battery 1 Remove all watches rings or other metal objects 2 Only use tools with insulated handles 3 Do not lay tools or metal parts on top of battery or any terminals 4 Wear protective eye wear goggles rubber gloves a...

Page 10: ...erruptible Power Supply Alarms Alarm Indication Unit Status Buzzer every 5 sec DC start Buzzer every 1 sec Self test 2 buzzer every 1 sec Low battery 4 beep every 2 4 sec Overload 3 buzzer every 1 sec Overheat Input is off long beep power off after 5 sec Short circuit ...

Page 11: ... at least 4 hours The battery is defective Contact Xtreme Power Conversion about replacement of batteries The UPS will not turn on The on off switch is designed to prevent damage by rapidly turning it off and on Turn the UPS off Wait 10 sec then turn the UPS on The UPS is not plugged into an AC wall outlet Connect the UPS to an 110 120V 60Hz AC wall outlet The battery is defective Contact Xtreme P...

Page 12: ...0 load 8 min 50 load Charge current 1 5A max PHYSICAL UPS dimensions W x D x H 3 7 x 14 6 x 6 2 in 4 9 x 16 9 x 8 7 in Shipping dimensions 6 1 x 16 2 x 10 2 in 7 5 x 18 9 x 12 8 in UPS weight 15 3 lbs 16 8 lbs 27 6 lbs 31 3 lbs Shipping weight 17 6 lbs 19 2 lbs 29 8 lbs 32 4 lbs Line cord 6 ft NEMA 5 15P Receptacles 6 NEMA 5 15R 3 surge protected 3 battery back up ENVIRONMENT Operating temperature...

Page 13: ...e Power Conversion Corporation XVT User s Manual Page 13 Uninterruptible Power Supply Shipping List 1 1 UPS 2 1 User s and Installation Manual 3 1 Intelligent monitoring software 4 1 USB computer port cable ...

Page 14: ...ask you for the above information and if possible help solve your problem over the phone In the event that the unit requires factory service the technician will issue you a Return Mate rial Authorization number RMA If you are returning the UPS to Xtreme Power for service please follow these procedures 1 Pack the UPS in its original packaging If the original packaging is no longer available ask the...

Page 15: ...pment is repaired or modified by anyone other than XPC Corporation or a XPC Corporation approved third party b the equipment is damaged by the customer is improperly used or stored is subjected to an adverse operating environment or is operated outside the limits of its electrical specifi cations or c the equipment has been used or stored in a manner contrary to the equipment s operating manual in...

Page 16: ...PC Limited Warranty against certain losses caused by a Power Disturbance for properly connected electronic equipment referred to as the Connected Equipment subject to certain terms and conditions provided below This policy applies only to the original purchaser of the Product If the Product is transferred or sold to another person or entity this policy is void Load Protection Policy Dollar and Per...

Page 17: ...d Protection Policy The following damage is not covered by this Policy 1 Restoration of lost data and reinstallation of software 2 Damage from a cause other than AC power line transients except for damage due to telephone line Local Area Network or CATV transients which is covered only if the Product offers such protection 3 DAMAGE CAUSED BY FAILURE TO PROVIDE A SUITABLE INSTALLATION ENVIRONMENT F...

Page 18: ...e payment to the Purchaser for either the cost of repair of the Connected Equipment or the Fair Market Value of the damaged Connected Equipment up to the dollar limits stated above XPC reserves the right to require the Purchaser to transfer title and deliver the Connected Equipment to XPC if it chooses to reimburse the Purchaser for the fair market value of the Connected Equipment XPCs maximum lia...

Reviews: