Uninterruptible Power Supply
Storage
Please adhere to the following instructions if the UPS is not installed immediately:
• Store the equipment as is in its original packing and shipping carton
• Do not store in temperatures outside the range of +15°C to +25°C.
• Ensure that the equipment is fully protected from wet or damp areas and from moist air.
In order to maintain the vitality of the batteries, ensure that the UPS is recharged every 6 months for at least 8
hours.
Installation
Environment
Ensure that all environmental concerns and requirements are met according to these technical specifications, oth
-
erwise the safety of installation personnel cannot be guaranteed and the unit may malfunction.
Ensure that you remember the following when locating the UPS system and battery options:
• Avoid extremes of temperature and humidity. Maximal battery life can be attained with a recommended
temperature range of 15 °C to 25 °C.
• Provide protection for the equipment from moisture.
• Space and ventilation requirements must be met. Ensure there is 100mm behind and 50mm on the sides
of the UPS for ventilation.
• Ensure that the front of the UPS remains clear for user operation.
The External Battery Cabinets has to be installed next to the UPS or under the UPS.
Installations with accessories of “Vertical” and “Wall-mounted” types:
Please install the vertical and wall-mounted types of units according to the following illustration.
5 in 1 RACK-MOUNT BRACKETS : 94A-VM1K-000*4 , 641-5008-410*16