Uninterruptible Power Supply
Software upgrade
There are two methods for software upgrade.
Use C2000 emulator to upgrade
When shutdown the UPS, remove the right panel of UPS, burn the DSP in control detection board
separately to upgrade. For detailed steps, please refer to the C2000 simulator instruction.
Use RS232 port to realize online upgrade
Remove the panel of the maintenance breaker, turn on the breaker so that the UPS goes to
maintenance bypass mode.
Turn on the UPS with utility. Open the serial program software Prg2800_33.exe
Note:
a) When burning is finished, the other DSP cannot be burned until the DSP buzz. ( after burning INV,
about 5S later, the next burning can be performed. When finish burning the REC, the next burning can
be executed after about 20s).
b) If it fails during the REC burning, it will show “ Program was
unsuccessful”. Switch off the UPS and then restart, click “Update” to re-burn.
c) If it fails during the INV burning, it will show “Program was
unsuccessful”. Switch off the UPS and then restart, modify the ID number to 1 in the software. Close the
serial port and then open it, click “Re-Update” to start the re-burning.
d) During the burning, it repeats a frame data which goes into
an infinite loop. Restart the UPS and Prg2800_33 and check if the communication connection is ok.
Then re-burn can be operated. If it is the REC burning, please refer to the item b, if INV burning, please
refer to item c.
e) If the REC and INV burning are both fail, the INV burning
(Re-Update) has to be operated firstly. Cut off the mains and then power on the UPS, then the REC
burning (Update) can be executed.