Power Cable
Please follow the local wiring regulations. Follow environmental conditions and refer to IEC60950-1.
AC input and output maximum current and power cable configuration.
Model
20KVA
40KVA
60KVA
Current (A)
60.1
120.2
180.3
Power cable (mm2)
16
50
95
Fixation torque force (lb-in)
20
20
20
Note:
Installer has to consider the max. current and wiring gauge when considering future extension.
DC input maximum current and power cable configuration.
Model
20KVA
40KVA
60KVA
Current (A)
98
196
294
Power cable (mm2)
25
95
150
Fixation torque force (lb-in)
20
20
20
Wiring
WARNING:
• Before wiring, make sure the AC input and battery power are completely cut off.
• Make sure the breakers, Main Breaker (Q1), Maintenance Breaker (Q2), Output Breaker (Q3) and battery
breaker are all in the OFF position.
Installation Drawing
Summary of Contents for M90
Page 11: ...Xtreme Power Conversion Corporation M90 User s Manual Page 11 Uninterruptible Power Supply ...
Page 72: ...Xtreme Power Conversion Corporation M90 User s Manual Page 72 Uninterruptible Power Supply ...
Page 73: ...Xtreme Power Conversion Corporation M90 User s Manual Page 73 Uninterruptible Power Supply ...
Page 76: ...Xtreme Power Conversion Corporation M90 User s Manual Page 76 Uninterruptible Power Supply ...
Page 77: ...Xtreme Power Conversion Corporation M90 User s Manual Page 77 Uninterruptible Power Supply ...