Xtreme Power Conversion Corporation
M90 User’s Manual
Page 26
Uninterruptible Power Supply
ECO Mode
The ECO Mode is enabled through the LCD setting menu. In ECO mode, the load is powered by bypass when the
bypass voltage and frequency are within the acceptable ranges. If the bypass is out of range, the UPS will transfer
the power source of load from bypass to inverter. In order to shorten the transfer time, the rectifier and inverter
are working when the UPS is in ECO mode.
ECO Mode Diagram
Maintenance Bypass Mode
When the UPS is in the off state and the utility power source is absent, the UPS will enter into shutdown mode.
Or when the UPS has discharged the battery to the cut-off level, the UPS will enter into shutdown mode as well.
When the UPS enters this mode, it is going to shut off the control power of UPS. The rectifier, charger and inverter
are all in off state.
Bypass
Main
Load
Rectifier
Inverter
STS
Q1
Input Breaker
Q2
Maintenance Breaker
Q3
Output Breaker
Battery Breaker
Inverter
Relay
Shutdown Mode Diagram
Summary of Contents for M90LU
Page 11: ...Xtreme Power Conversion Corporation M90 User s Manual Page 11 Uninterruptible Power Supply ...
Page 72: ...Xtreme Power Conversion Corporation M90 User s Manual Page 72 Uninterruptible Power Supply ...
Page 73: ...Xtreme Power Conversion Corporation M90 User s Manual Page 73 Uninterruptible Power Supply ...
Page 76: ...Xtreme Power Conversion Corporation M90 User s Manual Page 76 Uninterruptible Power Supply ...
Page 77: ...Xtreme Power Conversion Corporation M90 User s Manual Page 77 Uninterruptible Power Supply ...