Xtreme Power Conversion Corporation
M90 User’s Manual
Page 30
Uninterruptible Power Supply
Step 5:
Then, UPS will enter Battery Mode as shown in the diagram below.
Step 6:
Switch ON the output breaker (Q3). Cold start startup procedure is complete.
Maintenance Bypass Operation
Follow the instruction to transfer to Maintenance Bypass and UPS protection as below.
Transfer to Maintenance Bypass
Step 1:
Remove the mechanical lock plate of Maintenance Bypass Breaker.
Step 2:
Make sure the UPS operates in Bypass mode as shown below.
Summary of Contents for M90LU
Page 11: ...Xtreme Power Conversion Corporation M90 User s Manual Page 11 Uninterruptible Power Supply ...
Page 72: ...Xtreme Power Conversion Corporation M90 User s Manual Page 72 Uninterruptible Power Supply ...
Page 73: ...Xtreme Power Conversion Corporation M90 User s Manual Page 73 Uninterruptible Power Supply ...
Page 76: ...Xtreme Power Conversion Corporation M90 User s Manual Page 76 Uninterruptible Power Supply ...
Page 77: ...Xtreme Power Conversion Corporation M90 User s Manual Page 77 Uninterruptible Power Supply ...