Xtreme Power Conversion Corporation
M90 User’s Manual
Page 51
Uninterruptible Power Supply
Battery Low/
Shutdown SETTING
Battery Low Voltage
Set battery low voltage (10.5~11.5V)x(battery
Number)
• 11V x Battery Number (Default)
Battery Low Capacity
Set battery low capacity (20~50%)
• 20% (Default)
Battery Shutdown Voltage
Set battery voltage point for system shutdown
in battery mode (10.0~11V) x (battery Number)
• 10V x Battery Number (Default)
BATTERY TEST
Periodic Battery Test
Set periodic battery test disable or enable
• Disable (Default)
• Enable
Battery Test Interval
Set battery test interval (7~99 Days)
• 30 Days (Default)
Stop by Time
Set testing time for battery test (10~1000sec)
• 10 sec (Default)
Stop by Battery Voltage
Set stop battery voltage in battery test
(11~12V) x (battery Number)
• 11V x Battery Number (Default)
Stop by Battery Capacity
Set battery capacity to stop battery-testing.
(20~50%)
• 20% (Default)
Battery Age Alert
Battery Age Alert (Months)
Set battery age for replacement.
(Disable,12~60Months)
• Disable (Default)
If this feature is enabled and the battery has
been installed over this period, there is a warn
-
ing “Battery Age Alert” to indicate it.
Temperature Compensation
--
Set battery temperature compensation. (0~-5
(mV/°C/cl))
• 0(mV/°C/cl) (Default)
Pre-Alarm Screen
Use UP and DOWN buttons to switch different sub-menus. Press ENTER button to go into the Pre-Alarm setting
screen.
Setup-Pre-Alarm screen
Summary of Contents for M90LU
Page 11: ...Xtreme Power Conversion Corporation M90 User s Manual Page 11 Uninterruptible Power Supply ...
Page 72: ...Xtreme Power Conversion Corporation M90 User s Manual Page 72 Uninterruptible Power Supply ...
Page 73: ...Xtreme Power Conversion Corporation M90 User s Manual Page 73 Uninterruptible Power Supply ...
Page 76: ...Xtreme Power Conversion Corporation M90 User s Manual Page 76 Uninterruptible Power Supply ...
Page 77: ...Xtreme Power Conversion Corporation M90 User s Manual Page 77 Uninterruptible Power Supply ...