Xtreme Power Conversion Corporation
M90 User’s Manual
Page 52
Uninterruptible Power Supply
Pre-Alarm setting can be set in any operation mode
Setup-Pre-Alarm setting list
Setting Item
Sub Item
Explanation
Line Voltage Range
--
Set line voltage range:
Upper limit
• +5%
• +10%
• +15%
• +20% (Default)
Lower limit
• -5%
• -10%
• -15%
• -20% (Default)
Line Frequency Range
--
Set line frequency range:
Upper / Lower limit
• +/- 1Hz
• +/- 2Hz
• +/- 3Hz
• +/- 4Hz (Default)
Load
--
Set UPS Overload percentage (40~100%)
• 100% (Default)
Set UPS load unbalance percentage (20~100%)
• 100% (Default)
Information Screen
In INFORMATION menu, you can check the serial number, firmware versions, system configuration and settings of
the UPS. There are submenus under the INFORMATION, including Identification, System and Battery.
Information menu
INFORMATION screen