Xtreme Power Conversion Corporation
M90 User’s Manual
Page 6
Uninterruptible Power Supply
clearances are suggested:
• Keep a clearance of 39” from the top of the UPS for maintenance, wiring and ventilation.
• Keep a clearance of 16” from the back of the UPS and the external battery cabinets for ventilation.
• Keep a clearance of 36” from the front of the UPS and the external battery cabinets for maintenance and
ventilation.
8. For safety concerns, we suggest that you shall:
• Equip with CO2 or dry powder fire extinguishers near the installation area.
• Install the UPS in an area where the walls, floors and ceilings were constructed by fireproof materials.
9. Do not allow unauthorized personnel to enter the installation area. Assign specific personnel to keep the UPS
key.
Unpacking
1.
Use a forklift to move the product to installed area. Please make sure the bearing capacity of forklift is suf
-
ficient.
2.
Please follow the order in the figures below to remove carton and foams.