Xtreme Power Conversion Corporation
M90 User’s Manual
Page 64
Uninterruptible Power Supply
Warning! Battery Open
Battery not connected
1.
Check battery breaker.
2.
Check if the battery connection is well
connected.
3.
Check the setting of Nominal Battery
voltage.
4. Contact service personnel if necessary
Warning! Battery voltage High Battery voltage is too High
Check the setting of Nominal Battery voltage
and contact service personnel.
Warning! Module Un-Lock
As stated.
Check if module is locked well.
Warning! Turn On Abnormal
As stated.
Check if the input voltage or frequency is out
of range.
Warning! Charge Fail
As stated.
Contact service personnel.
Warning! EEPROM Fail
EEPROM operation error
Contact service personnel.
Warning! Fan Lock
As stated.
Check if the fan is blocked or contact service
personnel.
Warning! Line Phase Error
As stated.
Check if the Mains phase sequence is correct
and contact service personnel.
Warning! Bypass Phase Error
As stated.
Check if the Bypass phase sequence is cor
-
rect and contact service personnel.
Warning! N Loss
Neutral loss
Check if the Neutral connection is well and
contact service personnel..
Warning! Internal Initial Fail
As stated.
Contact service personnel.
Warning! Comm. Syn. Signal
Fail
Communicate Synchronization
Signal Fail
Contact service personnel.
Warning! Comm. TRIG0 Fail
Communicate Trigger signal
fault
Contact service personnel.
Warning! Redundancy Set Fail
As stated.
Check the redundancy setting is correct and
contact service personnel.
Warning! Parallel Sys Config.
Wrong
Parallel System Configure error
Contact service personnel.
Warning! Maintenance Bypass
Enter maintenance
Check if the connector is loose when it acts
abnormally.
Warning! Battery Age Alert
Battery Life expiration
Check if the battery has been used over its
service age. Or contact service personnel.
Warning! Parallel Rack Cable
Loosen
As stated.
Check if the Parallel Rack Cable is loose and
contact service personnel.
Warning! Parallel Rack Config.
Wrong
Parallel Rack Configure error
Check the Parallel Rack Setting is correct and
contact service personnel.
Warning! Parallel Firmware
Error
Power module parallel firm
-
ware error
The firmware version does not support Rack
Parallel feature. Contact service personnel.
Warning! ID Conflict
Power module ID conflict.
There are two Power Modules with the
same ID numbers. Change the repeated ID
to release it. Or contact service personnel.
Summary of Contents for M90LU
Page 11: ...Xtreme Power Conversion Corporation M90 User s Manual Page 11 Uninterruptible Power Supply ...
Page 72: ...Xtreme Power Conversion Corporation M90 User s Manual Page 72 Uninterruptible Power Supply ...
Page 73: ...Xtreme Power Conversion Corporation M90 User s Manual Page 73 Uninterruptible Power Supply ...
Page 76: ...Xtreme Power Conversion Corporation M90 User s Manual Page 76 Uninterruptible Power Supply ...
Page 77: ...Xtreme Power Conversion Corporation M90 User s Manual Page 77 Uninterruptible Power Supply ...