Xtreme Power Conversion Corporation
M90S-4S User’s Manual
Page 48
Uninterruptible Power Supply
Table 5-3: Setup-General setting list
Setting Item
Sub Item
Explanation
Model Name
Enter UPS Name (xxxxxxxxxx).
The max. Length is 10 characters.
Language
--
Provides 3 optional LCD languages:
English (Default)
Traditional Chinese
Simplified Chinese
TIME
Adjust Time
Set current date and time.
(yyyy / mm / dd hour : min : sec)
MUST be set after UPS installation
System Installed Date
Set system installed date
(yyyy / mm / dd)
2017/1/1 (Default)
MUST be set after UPS installation
System Last Maintain
Date
Set system latest maintenance date
(yyyy / mm / dd)
2017/1/1 (Default)
MUST be set after UPS installation
Battery Installed Date
Set battery installed date
(yyyy / mm / dd)
2017/1/1 (Default)
MUST be set after UPS installation
Battery Last Maintain
Date
Set battery latest maintenance date
(yyyy / mm / dd)
2017/1/1 (Default)
MUST be set after UPS installation
Change
Password
--
Change
Password
Audible
Alarm
Audible Mute
It is to mute the buzzer when UPS in any mode.
• Disable (Default)
• Enable
Battery Mute
It is to mute the buzzer when UPS in battery mode.
• Disable (Default)
• Enable
Fault Mute
It is to mute the buzzer when UPS in fault mode.
• Disable (Default)
• Enable
Bypass Mute
It is to mute the buzzer when UPS in bypass mode.
• Disable (Default)
• Enable
Factory
Reset
--
Restore to factory default setting
EPO Function
Set EPO active status
• Normal Close Active (Default)
• Normal Open Active