Uninterruptible Power Supply
BATTERY TEST
Periodic Battery Test
Set periodic battery test disable or enable
• Disable (Default)
• Enable
Battery Test Interval
Set battery test interval (7~99 Days)
• 30 Days (Default)
Battery Test Type
Set testing time for battery test (10~1000sec)
• Short Time(10S) (Default)
• Long Time(0.1M~0.9M)
• Long Time(1M~99M)
• Till Battery Low
Battery Age Alert
Battery Age Alert (Months)
Set battery age for replacement.
(Disable,12~60Months)
• Disable (Default)
If this feature is enabled and the battery has
been installed over this period, there is a warn-
ing “Battery Age Alert” to indicate it.
5.2.3 Pre-Alarm Screen
Use UP and DOWN buttons to switch different sub-menus. Press ENTER button to go into the Pre-Alarm setting
screen.
Figure 5-25 Setup-Pre-Alarm screen
Pre-Alarm setting can be set in any operation mode. See Setup-Pre-Alarm setting list in Table 5-6.