Xtreme Power Conversion Corporation
M90S-4S User’s Manual
Page 68
Uninterruptible Power Supply
However, it could execute this test in Line/Converter mode and reminder will pop up in the screen.
When “Yes” is selected, the screen will return back to home page with “Battery Test Mode” displayed
on top. If the test is completed, the displayed status will change back to UPS current mode. There are
four battery test types to select. Refer to Table 4-11.
Table 4-11: Battery Test Type
Setting Item
Sub Item
Explanation
Bat Test Type
Short Time
10-second test time.
Long Time
When testing time is longer than 1
minute, please select
“Long Time” and the duration is
able to set up.
(1~99min)
-10 min (Default)
Till to Bat Low
Test until the battery is low voltage.
b) On Battery Test mode, it will display “Cancel Test” in control menu. When “Cancel Test” is selected,
the screen will change back to UPS current mode.