Xtreme Power Conversion Corporation
M90S-4S User’s Manual
Page 74
Uninterruptible Power Supply
2) ECO setting(only available or effective on bypass mode, standby mode, Line mode and ECO
mode)
Interface
Description
ECO:
Status: Disable HighLoss
V: 240V LowLoss V: 218V
HighLoss F: 52Hz LowLoss
F: 48Hz
1. Status
Enable: Enable ECO Function
Disable: Disable ECO Function
If ECO function is disabled, voltage range and frequency range for ECO mode still
can be set, but it is meaningless unless the ECO function is enabled. The default
setting is Disable.
2. HighLoss V:
High voltage point in ECO mode.
For 3-3 10K, 3-1 10K and 1-1 10K models:
The setting range is from (Rated Output Volt +11V) to (Rated Output Volt +24V) and
the default setting is (Rated Output Volt +11V).
For 2-2 6K and 3-3 10K LV models:
The setting range is from (Rated Output Volt +6V) to (Rated Output Volt +12V) and
the default setting is (Rated Output Volt +6V).
3. LowLoss V:
Low voltage point in ECO mode.
For 3-3 10K, 3-1 10K and 1-1 10K models:
The setting range is from (Rated Output Volt -24V) to (Rated Output Volt-11V) and
the default setting is (Rated Output Volt -11V).
For 2-2 6K and 3-3 10K LV models:
The setting range is from (Rated Output Volt -12V) to (Rated Output Volt -6V) and
the default setting is (Rated Output Volt -6V).
4. HighLoss F:
Set High frequency point for ECO mode.
50 Hz system: Setting range is from 52Hz to 54Hz.
60 Hz system: Setting range is from 62Hz to 64Hz. The default value is 52Hz/62Hz.
5. LowLoss F:
Set Low frequency point for ECO mode.
50 Hz system: Setting range is from 46Hz to 48Hz.
60 Hz system: Setting range is from 56Hz to 58Hz. The default value is 48Hz/58Hz.