Xtreme Power Conversion Corporation
M90S-4S User’s Manual
Page 91
Uninterruptible Power Supply
M90S-6S
MODEL NUMBER
M90S-6S6K
M90S-6S12K
M90S-6S18K
M90S-6S24K
CAPACITY
Power Rating
6kVA/6kW
12kVA/12kW
18kVA/18kW
24kVA/24kW
INPUT
Voltage/Frequency
Nominal
120/208V or 120/240V
//
50/60Hz auto-sensing (2PH+N+G)
Voltage/Frequency Range
121–253VAC*
(L-L)
/ 40–70Hz
OUTPUT
Voltage & Frequency
120/208V or 120/240V &
50/60Hz ± 0.1Hz;
(2PH+N)
Efficiency / THD (full load)
Up to 98% ECO mode, 93% online mode / < 2%
Overload Capacity
105%-110% for 60min; 110%-125% for 10min; 126%-150% for 1min; >150% for 200ms
BATTERY SYSTEM
Nominal Voltage
+/-96V
Max charging (adjustable)
4A
8A
12A
16A
MODULE DIMEN-
SION
Power Module
16.3”W x 24”D x 5.2”H / 49.6 lbs
Battery Module
16.3”W x 24”D x 5.2”H / 115 lbs
SYSTEM ENCLOSURE Dimensions & Weight
17.4”W x 33.7”D x 45.5”H (UPS & BAT ENC) // UPS=180lbs / Battery=162lbs
Maximum Capacity
24kVA
Enclosure Capacity
6 Slots including 4 universal slots + 2 battery only slots
Optional Battery Enclo-
sure
7 Slots for additional battery modules
Output Connections
Terminal blocks and/or up to 4 receptacle panels
ENVIRONMENT
Temperature
0–40°C (32–104°F)**
Altitude
5,200 ft above sea level**
Audible noise
< 58dBA at 1m
APPROVALS
UL-1778 (TUV), cUL, FCC A, RoHS
WARRANTY
3 year electronics, 3 year battery (USA and Canada)
COMMUNICATIONS INTERFACE
RS-232, USB, Dry Contacts, EPO, (2) intelligent slot for optional cards (Web/SNMP, Relay,
Modbus)
INCLUDED IN BOX
User manual, USB cable, RS-232, ViewPower Software, anchor brackets
AVAILABLE OPTIONS
L14-30P Line Cord (6kVA), Receptacle Panels (2 max), Extended Battery Cabinet, 5 year
extended warranty, output distribution, 4-post rail kit, 2-post shelf kit.
*Depending on load level **Battery Life is reduced above 30°C, UPS Capacity derates above 30°C and 5,200 ft above sea level.