NXRi-6KL, NXRi-10KL USER MANUAL
UNINTERRUPTIBLE POWER SUPPLY (UPS)
Xtreme Power Conversion® (XPC) Corporation (Rev 2/7/13)
Page 40
03: Voltage Range for Bypass
Interface
Setting
Parameter 2:
Set the acceptable low voltage for bypass.
Setting range is from 110V to 209V and the default value is
110V.
Parameter 3:
Set the acceptable high voltage for bypass.
Setting range is from 231V to 276V and the default value is
264V.
04: Frequency Range for Bypass
Interface
Setting
Parameter 2:
Set the acceptable low frequency for bypass.
50 Hz system: Setting range is from 46.0Hz to 49.0Hz.
60 Hz system: Setting range is from 56.0Hz to 59.0Hz.
The default value is 46.0Hz/56.0Hz.
Parameter 3:
Set the acceptable high frequency for bypass.
50 Hz: Setting range is from 51.0Hz to 54.0 Hz.
60 Hz: Setting range is from 61.0Hz to 64.0Hz.
The default value is 54.0Hz/64.0Hz.
05: ECO Mode enable / disable
Interface
Setting
Parameter 3:
Enable or disable ECO function. You may choose
following two options:
DIS:
disable ECO function
ENA:
enable ECO function
If ECO function is disabled, voltage range and frequency range
for ECO mode still can be set, but it is meaningless unless the
ECO function is enabled.
06: Voltage Range for ECO Mode
Interface
Setting
Parameter 2:
Low voltage point in ECO mode. The setting
range is from 5% to 10% of the nominal voltage.
Parameter 3:
High voltage point in ECO mode. The setting
range is from 5% to 10% of the nominal voltage.