background image

NXRi-6KL, NXRi-10KL USER MANUAL 

 

UNINTERRUPTIBLE POWER SUPPLY (UPS) 

 
Xtreme Power Conversion® (XPC) Corporation (Rev 2/7/13) 

Page 13 

 

NXRi-10KL UPS REAR VIEW DIAGRAM (WITH PARALLEL FUNCTION) 

 

NXRi-10KL UPS REAR VIEW WIRING DIAGRAM 

Summary of Contents for NXRi-6KL

Page 1: ...www xpcc com 2013 Xtreme Power Conversion Corporation All rights reserved UNINTERRUPTIBLE POWER SUPPLY UPS NXRi Online High Voltage Rack Models USER INSTALLATION MANUAL...

Page 2: ...ine Technology 10 Diagnostic Tests 10 SYSTEM CONFIGURATION 11 LED LCD Descriptions 15 RS 232 Standard Interface 16 SNMP Communications Option 16 Remote Emergency Power Off REPO Port 16 HARDWARE INSTAL...

Page 3: ...the Batteries 33 Turn off the UPS with Utility Power in AC Mode 33 Turn off the UPS without Utility Power in Battery Mode 33 Muting the Buzzer 33 Operation in Warning Status 33 Operation in Fault Mode...

Page 4: ...le Output Settings 42 11 Shutdown Point for Programmable Output 42 12 Hot standby function enable disable 43 13 Battery Voltage Adjustment 43 14 Charger Voltage Adjustment 43 15 Output Voltage Adjustm...

Page 5: ...NXRi 6KL NXRi 10KL USER MANUAL UNINTERRUPTIBLE POWER SUPPLY UPS Xtreme Power Conversion XPC Corporation Rev 2 7 13 Page 5...

Page 6: ...it provides important information that should be followed during installation and maintenance of the UPS and batteries allowing you to correctly set up your system for the maximum safety and performa...

Page 7: ...CAUTION Do not dispose of batteries in a fire the battery may explode CAUTION Do not open or mutilate the battery released electrolyte is harmful to the skin and eyes CAUTION A battery can present a r...

Page 8: ...ualified service personnel Before conducting any maintenance repair or shipment first ensure that everything is turned off completely and disconnected For additional safety instructions please use the...

Page 9: ...ns It also includes information on how to ship store handle and install the equipment Only detailed requirements of the UPS units are described herein and installation must be carried out in accordanc...

Page 10: ...es for their maximum potential In the event that the power failure lasts longer than the UPS backup time the UPS will shut down avoiding battery damage When the input AC voltage returns the UPS will a...

Page 11: ...consideration The total demand of the protected system shall dictate the output power rating VA Allow a margin for future expansion or calculation inaccuracies from measured power requirements Backup...

Page 12: ...NXRi 10KL USER MANUAL UNINTERRUPTIBLE POWER SUPPLY UPS Xtreme Power Conversion XPC Corporation Rev 2 7 13 Page 12 NXRi 6KL UPS REAR VIEW DIAGRAM WITHOUT PARALLEL FUNCTION NXRi 6KL UPS REAR VIEW WIRING...

Page 13: ...NXRi 10KL USER MANUAL UNINTERRUPTIBLE POWER SUPPLY UPS Xtreme Power Conversion XPC Corporation Rev 2 7 13 Page 13 NXRi 10KL UPS REAR VIEW DIAGRAM WITH PARALLEL FUNCTION NXRi 10KL UPS REAR VIEW WIRING...

Page 14: ...NXRi 6KL NXRi 10KL USER MANUAL UNINTERRUPTIBLE POWER SUPPLY UPS Xtreme Power Conversion XPC Corporation Rev 2 7 13 Page 14 NXRi EBP20 REAR VIEW DIAGRAM FRONT PANEL...

Page 15: ...er to the Operations section of this document Bypass LED Illuminates during UPS Startup Bypass Mode Battery Test and ECO Mode of operation Line LED Illuminates during UPS Startup AC Mode CVCF Mode Bat...

Page 16: ...intelligent network card can be compatible with popular software and hardware found on the web and in operating systems It can support operating systems such as HP Open View IBM Netview SUN Netmanager...

Page 17: ...arton Do not store in temperatures outside the range of 15 C to 25 C Ensure that the equipment is fully protected from wet or damp areas and from moist air In order to maintain the batteries the UPS s...

Page 18: ...he following when locating the UPS system and battery options Avoid extremes of temperature and humidity Maximum battery life can be attained with a recommended temperature range of 15 C to 25 C Provi...

Page 19: ...TERRUPTIBLE POWER SUPPLY UPS Xtreme Power Conversion XPC Corporation Rev 2 7 13 Page 19 Step 1 Use 4 screws to mount right and left rail sliders in front of rack Step 2 Use 4 screws to mount right and...

Page 20: ...WER SUPPLY UPS Xtreme Power Conversion XPC Corporation Rev 2 7 13 Page 20 Step 3 Place the nuts in the proper location in the rack based upon height of UPS Step 4 Carefully place the UPS on the rail s...

Page 21: ...rated current is less than the UPS maximum input current 2 Switch off the utility circuit breaker before installation 3 Turn off all connected devices before connecting to the UPS 4 Wiring sizes shoul...

Page 22: ...tend the backup time to critical devices by setting shorter backup time for non critical devices Note Please install an output breaker between the output terminal and the load The breaker should be qu...

Page 23: ...rsion XPC Corporation Rev 2 7 13 Page 23 5 Remove the cover of the parallel share current cable port on the UPS Connect each UPS one by one with the parallel cable and share current cable Reattach the...

Page 24: ...e you modify the setting simultaneously The connection with wrong battery voltage may cause permanent damage to the UPS Make sure the voltage of the battery pack is correct Attention should be paid to...

Page 25: ...nstallation Follow the basic procedures for UPS rack installation if required A rail kit should be used with each battery pack when being installed in a 4 post rack Then make the connections as shown...

Page 26: ...re than 0 5s to turn off the UPS Esc key Press this button to return to last menu in setting menu Test Up Button Battery test Press and hold the button more than 0 5s to test the battery while in AC m...

Page 27: ...2 7 13 Page 27 LED Indicators There are 4 LEDs on the front panel to show the UPS working status Mode LED Bypass Line Battery Fault UPS Startup Bypass mode AC mode Battery mode CVCF mode Battery Test...

Page 28: ...sabled Output Battery voltage information Indicates the output voltage frequency or battery voltage Vac output voltage Vdc battery voltage Hz frequency Load information Indicates the load level by 0 2...

Page 29: ...unction Battery information Indicates the Battery capacity by 0 25 26 50 51 75 and 76 100 Indicates the battery is not connected Indicates low battery level and low battery voltage Input Battery volta...

Page 30: ...Over charge EPO enable Fan failure Over temperature Charger failure IP fuse broken Overload 3 times in 30min EPO status Cover of maintenance bypass switch open Parallel protection Fault Bus start fai...

Page 31: ...power is abnormal the UPS will operate in Battery Mode without interruption Note When the UPS is running out of battery time it will shut down automatically at Battery Mode When the utility power is...

Page 32: ...batteries at least 10 hours before use to assure proper backup time 3 Make sure the battery number setting on the control board is consistent to the real connection Battery Mode Operation 1 When the U...

Page 33: ...rminals even though the UPS inverter has been turned off Note After turning off the UPS please beware that the UPS is operating in Bypass Mode and there is a risk of power loss for connected devices 2...

Page 34: ...the UPS If the load cannot be shut down remove the cover from the Maintenance Bypass Switch on the rear panel of the UPS and turn the Maintenance Bypass Switch to BPS position 3 Switch off the input b...

Page 35: ...rrent cables are connected well If they are all connected well the UPS may have an internal issue Contact your distributor for further assisatance 6 Turn off each UPS in sequence After all of the UPS...

Page 36: ...em will transfer to Bypass mode Remove all maintenance bypass covers and sent the maintenance switches from UPS to BPS Turn off the input breakers and battery breakers 3 Remove the desired UPS 4 Turn...

Page 37: ...ersion XPC Corporation Rev 2 7 13 Page 37 Abbreviations in LCD Display Abbreviation Display content Meaning ENA Enable DIS Disable ATO Auto BAT Battery NCF Normal mode not CVCF mode CF CVCF mode SUB S...

Page 38: ...t for parameter 1 Code Description Bypass AC ECO CVCF Battery Battery Test 01 Output voltage Y 02 Output frequency Y 03 Voltage range for bypass Y 04 Frequency range for bypass Y 05 ECO mode enable di...

Page 39: ...rmal utility frequency If it is from 46Hz to 54Hz the output frequency will be 50 0Hz If it is from 56Hz to 64Hz the output frequency will be 60 0Hz ATO is default setting Parameter 3 Frequency mode S...

Page 40: ...0Hz to 59 0Hz The default value is 46 0Hz 56 0Hz Parameter 3 Set the acceptable high frequency for bypass 50 Hz Setting range is from 51 0Hz to 54 0 Hz 60 Hz Setting range is from 61 0Hz to 64 0Hz The...

Page 41: ...ass allowed When selected UPS will run at Bypass mode depending on bypass enabled disabled setting FBD Bypass not allowed When selected it s not allowed for running in Bypass mode under any situations...

Page 42: ...nversion XPC Corporation Rev 2 7 13 Page 42 10 Programmable Output Settings Interface Setting This function not supported in this model 11 Shutdown Point for Programmable Output Interface Setting This...

Page 43: ...Voltage Adjustment Interface Setting Parameter 2 Select Add or Sub function to adjust battery voltage to real figure Parameter 3 the voltage range is from 0V to 5 7V the default value is 0 09V 14 Char...

Page 44: ...or 003 The assigned numbers may be changed dynamically in the operation Operating mode status AC mode Description When the input voltage is within acceptable range UPS will provide pure and stable AC...

Page 45: ...tion When input voltage is within acceptable range and bypass is enabled turn off the UPS and it will enter Bypass mode Alarm beeps every two minutes LCD display Battery Test Description When UPS is i...

Page 46: ...r fault 1A None Bus over 02 None Battery SCR short circuited 21 None Bus under 03 None Inverter relay short circuited 24 None Bus unbalance 04 None Parallel communication failure 35 None Inverter soft...

Page 47: ...Beeping every second Overload Beeping twice every second Battery not connected Beeping every second Overcharge Beeping every second EPO enabled Beeping every second Fan failure Over temperature Beepi...

Page 48: ...display and alarm beeps continuously Battery voltage is too low or the charger is fault Contact your dealer The icon and flash on LCD display and alarm beeps twice every second UPS is overload Remove...

Page 49: ...oad is still supplied but directly from AC power via bypass 2 The load is no longer supplied by power Contact your dealer Battery backup time is shorter than nominal value Batteries are not fully char...

Page 50: ...e UPS after disabling the warning message by pressing UP and DOWN buttons at the same time Otherwise DO NOT turn on UPS and contact your dealer for assistance For single UPS since there is not communi...

Page 51: ...well away from the batteries Verify that no voltage between the battery terminals and the ground is present before maintenance or repair In this product the battery circuit is not isolated from the in...

Page 52: ...pen or mutilate the batteries Released electrolyte is harmful to skin and eyes and may be toxic CAUTION Although the battery system voltage is only 12VDC and 24VDC the battery can present a high risk...

Page 53: ...RY Battery Type EBP20 20 12V 9AH Recharge to 90 3 hours 4 hours Backup Time half full 18 min 7 min 12 min 5 min Charge Current 2A PHYSICAL UPS Dimensions W x D x H 438 x 580 x 133 mm 17 2 x 22 8 x 5 2...

Page 54: ...NXRi EBP20 137 56 34 23 WITH 3 NXRi EBP20 230 95 56 39 WITH 4 NXRi EBP20 332 137 81 56 NXRi 10KL WITH 1 NXRi EBP20 29 12 7 5 WITH 2 NXRi EBP20 71 29 17 12 WITH 3 NXRi EBP20 120 49 29 20 WITH 4 NXRi E...

Page 55: ...e protected equipment including model numbers if possible A technician will ask you for the above information and if possible help solve your problem over the phone In the event that the unit requires...

Reviews: