Xtreme Power Conversion Corporation
P90L 6kVA & 10kVA User’s Manual
Page 23
Uninterruptible Power Supply
2) ECO setting (only available or effective on bypass mode)
Interface
Description
1.
Status
Enable:
Enable ECO Function
Disable:
Disable ECO Function
If ECO function is disabled, voltage range and frequency range for
ECO mode can still be set, but it is meaningless unless the ECO func
-
tion is enabled.
2.
HighLoss V:
High voltage point in ECO mode. The setting range is
from +5% to +10% of the nominal voltage.
3.
LowLoss V:
Low voltage point in ECO mode. The setting range is from
-5% to -10% of the nominal voltage.
4.
HighLoss F:
Set low frequency point for ECO mode.
50 Hz system: Setting range is from 46Hz to 48Hz.
60 Hz system: Setting range is from 56Hz to 58Hz.
The default value is 48Hz/58Hz.
5.
LowLoss F:
Set high frequency point for ECO mode.
50 Hz: Setting range is from 52.0Hz to 54.0 Hz.
60 Hz: Setting range is from 62.0Hz to 64.0Hz.
The default value is 52.0Hz/62.0Hz.
3) Output setting (only available or effective on bypass mode)
Interface
Description
1.
Volt:
208:
The voltage is set for 208VAC
220:
The voltage is set for 220VAC
230:
The voltage is set for 230VAC
240:
The voltage is set for 240VAC
2.
Freq:
50Hz:
The output frequency is manual set for 50Hz.
60Hz:
The output frequency is manual set for 60Hz.
ATO:
If selected, output frequency will be decided according to the
latest normal utility frequency. If it is from 46Hz to 54Hz, the output
frequency will be 50.0Hz. If it is from 56Hz to 64Hz, the output fre
-
quency will be 60.0Hz. ATO is default setting.
3.
CVCF:
Used to enable or disable frequency converter mode.
Enable:
The output frequency will be fixed at 50Hz or 60Hz accord
-
ing to setting of “Freq”. The input frequency could be from 46Hz to
64Hz.
Disable:
The output frequency will synchronize with the input fre
-
quency within 46~54 Hz for 50Hz system or within 56~64 Hz for 60Hz
system.
Note:
CVCF means Constant Voltage and Constant Frequency, it rep
-
resents frequnecy converter mode.