Xtreme Power Conversion Corporation
P90L 6kVA & 10kVA User’s Manual
Page 38
Uninterruptible Power Supply
This unit can either be mounted horizontally in a rack or placed vertically on the floor.
Rack Installation
Tower Installation
Connecting with UPS and Other Battery Box
Follow below installation diagram to connect with UPS and other battery box with included cable.
Storage & Maintenance
The unit contains no user-serviceable parts. If the battery service life (3~5 years at 25°C ambient temperature) has
been exceeded, the batteries must be replaced. In this case, please contact your dealer.
Storage
Before storing, charge the unit 4 hours. Store the unit covered and upright in a cool, dry location. During storage,
recharge the battery in accordance with the following table:
Storage Temperature
Recharge Frequency
Charging Duration
-25°C - 40°C
Every 3 months
1-2 hours
40°C - 45°C
Every 2 months
1-2 hours
UPS
1st battery pack
2nd battery pack
Be sure to deliver the spent battery to a recycling facility or
ship it to your dealer in the replacement battery packing material.