Xtreme Power Conversion Corporation
P90L 6kVA & 10kVA User’s Manual
Page 16
Uninterruptible Power Supply
2.
In Battery mode, you can mute the alarm by entering ”Control->Mute” on LCD to silence it. Please refer
to the section of “LCD operation”.
3. The backup time depends on the external battery capacity.
4.
The backup time may change under different environment temperature and load type.
5. The maximum backup time is limited by default to 16.5 hours (After discharging 16.5 hours, UPS will shut
down automatically to protect the battery). The time could be modified through LCD panel or communica
-
tion port.
Test the batteries
1.
If you need to check the battery status or performance when the UPS is running in Line / Converter / ECO
mode, you could enter ”Control->Batt Test” to instruct the UPS to perform a battery test. Please refer to
the section of “LCD Operation”.
2.
Users also can set battery test through monitoring software.
3. If the UPS is in battery testing, “Battery test mode” will be displayed on LCD, the buzzer indication will be
the same as Battery mode, but both line LED and battery LED will be lit.
Turn off the UPS with utility power supply in Line mode
1.
When LCD is on home page, press the “OFF/ESC” button, LCD will show a prompt page of “Turn
Off”; Move the arrow to “Yes” by up or down button, then press “ON/ENTER”, the UPS will beep
once and turn off. Power is still applied via bypass mode. You could also enter the “control menu” to
select the instruction “Turn Off” to turn off the UPS. Please refer to the section of “LCD operation”.
Note:
Here, “Turn Off” means that UPS is not working on line / converter / ECO / battery / battery test
mode. So even though the UPS is turned off, if input or bypass voltage is normal, the internal power sup
-
ply will still be working; and if bypass status has been set to “enable”, the output voltage of the UPS will
still exist.
2.
If you need to fully cut off the output, switch off the external input breaker. A few seconds later, there is
no display shown on the panel and UPS is completely off.
Turn off the UPS without utility power supply in Battery mode
1.
When LCD is on home page, press the “OFF/ESC” button, LCD will show a prompt page of “Turn Off”; Move
the arrow to “Yes” by up or down button, then press “ON/ENTER”, the UPS will beep once and turn off.
Power is still applied via bypass mode. You could also enter the “control menu” to select the instruction
“Turn Off” to turn off the UPS. Please refer to the section of “LCD operation”.
2.
If there is no bypass input voltage, the UPS will cut off all power supply and there is no display shown on
the panel.